Advanced power quality analyzers (according Standard UNE-EN-50160 and IEC 61000-4-30)

IO8R

IO8R, Advanced power quality analyzers

Code: Q20903.CONSULTAR DISPONIBILIDAD

  • Protocol: Modbus/TCP | ZMODEM | FTP | webserver (HTTP)
  • Memory: 4 GB
  • Memory: Yes
  • Web server: Yes
  • Communications: RS-232 | RS-485 | Ethernet
  • Nº relays: 8
  • Digital inputs: 8

INFORMATION

Description

QNA 500 is a modular power quality analyzer designed to measure and record the main electrical parameters and transient disturbances. The measurement is taken in true root mean square (TRMS), with 5 AC voltage inputs, 4 AC current inputs (via ... /5 A current transformers) and a leakage current input.

Applications

QNA 500 is designed to supervise the electric installation and problems relating to electric power quality, in order to control production processes and manage incidents. It integrates easily with SCADA applications and interacts with commercially available PLCs, and so can be part of more global data acquisition systems and report to users the information they require at any time. Its modularity and the addition of M-IO8 modules enable the user to also control energy consumption, states of switches or loads, send alarms, and even connect/disconnect loads according to configurable conditions.
When combined with CIRCUTOR PowerVision Plus software, the user can configure customised reports to assess the correct running of the electric installation, and can apply standards such as the EN-50160, event tables such as CBEMA, UNIPEDE or others. By automating this information, the user can view the most important data needed for the relevant analysis with just one click .

SPECIFICATIONS

AC power supply
Consumption
10 VA
Digital relay outputs
Type
Relay
Nominal voltage
250 V~ / 30 Vdc
Nominal current
6 A
Maximum load VAC
6 A (250 V~ resistive)
Maximum load VDC
6 A (30 Vdc)
Digital inputs
Quantity
8
Type
Optocoupler
Input/output insulation
5 kV
Operating voltage
12-18 Vdc
Minimum signal width
15 µs
Consumption (per input)
2,5 mW
Serial communication
Protocol
Modbus RTU
Environmental characteristics
Working temperature
-10…+60 ºC
Relative humidity (without condensation)
5…95%
Protection class
IP 41
Mechanical characteristics
Envelope
Self-extinguishing V0 plastic
Fastening
DIN rail 46227 (EN 50022) or Bottom Panel
Differential current measurement
≤ 2,5 mm2
Weight (kg)
0,49
Size (mm) width x height x depth
62 x 125 x 173.3 (mm)
Standards
Standards
EN 61000-6-3, EN 61000-6-1, EN 61010-1, EN 61000-4-11, EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5
Certifications
CE
Electrical safety, Installation category
CAT III 280V, IEC 61010
Electrical safety, Maximum height (m)
2000
Electrical safety
Insulation
Double-insulated electric shock protection class II (IEC 61010-1)

DIMENSIONS

CONNECTIONS

VIDEOS

DOWNLOADS

User's manual
Technical guide
Dimensions
Datasheet
CE-certified