Static Var Generator with multilevel technology

SVGm-3WF-30M-480

SVGm-3WF-30M-480, Static Var Generator with multilevel technology

Code: R4P3M0.

  • EMI filter: 1
  • System: 3 wires, 230...480 V
  • kvar (230 V): 17,4
  • kvar (400 V): 30
  • kvar (440 V): 30
  • kvar (480 V): 30
  • Phase current: 44
  • Use voltage (V): 480

INFORMATION

Description

SVGm cabinet-type static var generators are the most accurate power factor correction solution in both unbalanced three-phase systems and installations with inductive and capacitive reactive power. They can be used in three-phase industrial, commercial or service installations, and they are not affected by the installation's harmonics. Much safer device with minimal maintenance. This product range features rack assembly in standard cabinets, designed to simplify installation.

The implemented characteristics and functions are as follows:

  • Power factor correction (inductive/capacitive) from 30 to 100 kvar (3W) and 20 to 69 kvar (4W) per cabinet.
  • The 100 kvar (3W) and 69 kvar (4W) rack-type module's compact dimensions make it easy to install in standard cabinets.
  • Multi-range voltage and frequency (50/60 Hz).
  • Harmonic current immunity.
  • Cos φ range from 0.7 inductive...to...0.7 capacitive.
  • Web-based performance monitoring.
  • Internal short-circuit protection.

If higher reactive power compensation capacity is required, up to 100 devices can be connected in parallel.

Applications

Ideal solution for individual loads or installations with numerous single-phase and three-phase loads, whether inductive or capacitive. Also, for installations whose load fluctuates over short time frames. Typical loads would be overhead cranes, welding equipment, lifts, drilling/shredding systems, data centres.

SPECIFICATIONS

AC power supply
Nominal voltage
208 … 480 V~ F-F (± 10 %)
Frequency
50 / 60 Hz ± 5 %
Consumption
650 W (Consumo máximo)
Electrical characteristics
Maximum phase current
44 A (RMS)
Earthing system
TN, TT
Current measurement circuit
Consumption
1,5 VA por transformador
Transformation ratio
Transformer: 5/5A … 5000/5A
Serial communication
Technology / Type
RS-485
Protocol
Modbus/RTU
Communication Network
Technology / Type
Ethernet
Protocol
TCP/IP, Modbus TCP
Environmental characteristics
Working temperature
-10 … +45 ºC
Storage temperature
-20 … +50 ºC
Relative humidity (without condensation)
0 …. 95 %
Protection class
IP20
Mechanical characteristics
Noise
58 dBA, 1m from the mounting wall, ISO 11201:2010 V2 certified
Weight (kg)
21
Size (mm) width x height x depth
430 x 530 x 178 (mm)
Features / performance
Filtering / Response time
< 100 µs
Reactive power compensation (Kvar)
Selectable: 0.7 inductive ... 1 ... 0.7 capacitive
Parallel assembly/installation
Up to 100 devices of different caliber. Connection of transformers only in Master unit.
Standards
Standards
IEC 61000-6-4, UNE-EN 55011, IEC 61000-6-2, IEC 62477-1, IEC 61439-1, IEC 60721-3-3 (Indoor conditioned)
Electrical safety, Maximum height (m)
3000 (2000 m sin limitar prestaciones)

DIMENSIONS

CONNECTIONS

VIDEOS

DOWNLOADS

User's manual
3D
Dimensions
Diagram connection
Configuration guide
Datasheet
CE-certified
Other Certificates
Catalogue
Leaflet

ACCESORIES

TAMBIÉN TE PUEDE INTERESAR