Residual current protection and self-reclosing

REC4-4P-63-300

REC4-4P-63-300, RCCB with self-reclosing system, type A

Code: P26F33.

  • Poles: 4
  • In (A): 63 A
  • Reclosing mode: Time
  • Sensitivity: 300 mA
  • Breaking element: built-in
  • Type of protection: Type A

INFORMATION

Description

The REC4 family comprises 2- or 4-pole residual current circuit breakers paired with an intelligent automatic reclosing motor, which enables safe reclosing of the associated residual current circuit breaker.
The REC4C version can signal a lockout when the maximum number of reclosing attempts has been reached, by means of a status output. 

Compact device, installed like a residual current circuit breaker. No interconnections between the motor and the residual current circuit breaker are required.

The time-based reclosing mode ensures continuity of electric supply. The device has a lockout system that determines whether it operates in manual or automatic mode (reclosing enabled).

Applications

All electrical installations where full continuity of the electricity supply is required in the event of unforeseen situations that cause residual current protection devices to trip for reasons unrelated to electrical insulation.

  • Residential sector, refrigerators, alarms, garage doors.
  • Services sector, air conditioning, cold rooms, lighting, UPS, etc.
  • Industrial sector, control of critical production processes.

SPECIFICATIONS

AC power supply
Nominal voltage
230 V ~ (± 20 %)
Frequency
50/60 Hz (± 5 %)
Consumption
5 VA
Installation category
CAT III 300 V
User interface
LED
2 LED: AUTO, color green / REC, color red
Environmental characteristics
Working temperature
Earth leakage protection: -25 … +55 ºC Reclosing: -10 … +55 ºC
Storage temperature
-35 … +65 ºC
Relative humidity (without condensation)
5 … 95 %
Protection class
IP 20
Mechanical characteristics
Envelope
Plastic V0 polycarbonate
Fastening
DIN rail
Weight (kg)
0,41
Size (mm) width x height x depth
90.5 x 103 x 81 (mm)
Differential protection
Type
Type A
Sensitivity (I∆n), A
0,3
Delay time (t∆)
INS
Reclosure type
Reset time
10/20/60 s
Reclosure time
< 3/20/180 s
Reclosure number
3
Circuit breaker / RCCB
Rated nominal voltage (Un)
400 V ~
Rated breaking and re-closure capacity (Im)
500 A
Assigned frequency (Hz)
50/60
Rated conditional short-circuit current (Inc)
10 kA to 230/400V with gB 80A fuse
Shock wave resistance
Class A, AC: 250A 8/20μs Class S: 3000A 8/20μs
Nominal current (In)
63 A
Standards
Standards
UNE-EN 61008-1, UNE-EN 63024
Electrical safety, Installation category
CAT III 300 V ~
Electrical safety, Contamination level/class
Pollution resistance 2
Electrical safety, Maximum height (m)
2000

DIMENSIONS

CONNECTIONS

VIDEOS

DOWNLOADS

User's manual
Technical guide
3D
Dimensions
Diagram connection
Datasheet
CE-certified
Leaflet
Presentation

ACCESORIES