Residual current protection and self-reclosing

REC4-4P-40-300

REC4-4P-40-300, RCCB with self-reclosing system, type A

Code: P26F23.

  • Poles: 4
  • In (A): 40 A
  • Reclosing mode: Time
  • Sensitivity: 300 mA
  • Breaking element: built-in
  • Type of protection: Type A

SPECIFICATIONS

AC power supply
Nominal voltage
230 V ~ (± 20 %)
Frequency
50/60 Hz (± 5 %)
Consumption
5 VA
Installation category
CAT III 300 V
User interface
LED
2 LED: AUTO, color green / REC, color red
Environmental characteristics
Working temperature
Earth leakage protection: -25 … +55 ºC Reclosing: -10 … +55 ºC
Storage temperature
-35 … +65 ºC
Relative humidity (without condensation)
5 … 95 %
Protection class
IP 20
Mechanical characteristics
Envelope
Plastic V0 polycarbonate
Fastening
DIN rail
Weight (kg)
0,4
Size (mm) width x height x depth
90.5 x 103 x 81 (mm)
Differential protection
Type
Type A
Sensitivity (I∆n), A
0,3
Delay time (t∆)
INS
Reclosure type
Reset time
10/20/60 s
Reclosure time
< 3/20/180 s
Reclosure number
3
Circuit breaker / RCCB
Rated nominal voltage (Un)
400 V ~
Rated breaking and re-closure capacity (Im)
500 A
Assigned frequency (Hz)
50/60
Rated conditional short-circuit current (Inc)
10 kA to 230/400V with gB 80A fuse
Shock wave resistance
Class A, AC: 250A 8/20μs Class S: 3000A 8/20μs
Nominal current (In)
40 A
Standards
Standards
UNE-EN 61008-1, UNE-EN 63024
Electrical safety, Installation category
CAT III 300 V ~
Electrical safety, Contamination level/class
Pollution resistance 2
Electrical safety, Maximum height (m)
2000

DIMENSIONS

CONNECTIONS

VIDEOS

DOWNLOADS

User's manual
Technical guide
3D
Dimensions
Diagram connection
Datasheet
Presentation
CE-certified