Single-phase Power quality analyzer

VLOG-10

VLOG-10, Single-phase analyzer to collect and record outages, gaps, overvoltages and voltage load profile,

Code: M84101.

    INFORMATION

    Description

    VLOG-10 is a portable Power Quality Analyser, whose purpose is to capture the main voltage waveform events (power failure, gaps and overvoltages). This programmable measuring device measures, calculates and stores the network voltage, monitoring different events that may be produced in the single-phase network. The VLOG-10 gives true root mean square (True-RMS) measurement by means of the power supply voltage, storing the results in its 512kb internal memory for subsequent data dumping and study.

    The device is designed to operate autonomously once it has been connected to the mains, after which it immediately starts to measure the mains voltage and frequency, recording the data and incidences that have occurred. These records are stored according to the configuration previously set by the user in the configuration parameters. The dumped generated data is downloaded via the built-in USB interface.

    Applications

    • Power quality analyser for single-phase networks of up to 265 V~.
    • Suitable for controlling the voltage of residential or domestic type electrical networks.
    • Suitable for large-scale projects, for power quality recording.
    • Compact dimensions, and suitable for installation in double insulated boxes, next to the electricity billing meter (the energy supplier's meter).

    SPECIFICATIONS

    AC power supply
    Nominal voltage
    85…265 V~
    Frequency
    50 / 60 Hz.
    Consumption
    0,8…1,12 VA
    Installation category
    CAT III 300 V
    Battery specification
    Type
    Li/MnO2
    Voltage
    3 Vcc
    Performance-guarantee
    10 años
    Capacity
    220 mAh
    Voltage measurement circuit
    Voltage measuring range
    85…265 V~
    Minimum measurement voltage (Vstart)
    85 V~
    Installation category
    CAT III 300 V
    Measurement accuracy
    Phase voltage measurement
    0,5 % (accuracy within the range +5 … +45 °C)
    Active power measurement (kW)
    Class 0.5 ± 1 digit (IEC 61557-12) (Vn a.c. 230/110)
    Power factor measurement
    Class 0.5 (IEC 61557-12)
    User interface
    LED
    3
    Connectivity
    USB tipo B
    Keyboard
    1 pushbutton
    Environmental characteristics
    Working temperature
    -10 … +55 °C
    Storage temperature
    -20 … +80 °C
    Relative humidity (without condensation)
    25 … 75 %
    Protection class
    IP 20
    Mechanical characteristics
    Envelope
    Self-extinguishing V0 plastic
    Weight (kg)
    0,1
    Size (mm) width x height x depth
    43 x 116 x 26 (mm)
    Standards
    Standards
    IEC 61010-1, IEC 61326-1
    Certifications
    CE
    Electrical safety, Installation category
    CAT III 300 V, IEC 61010
    Electrical safety, Maximum height (m)
    2000

    DIMENSIONS

    CONNECTIONS

    VIDEOS

    DOWNLOADS

    User's manual
    Technical guide
    Datasheet
    CE-certified
    Software & Firmware

    ACCESORIES