Portable power analyzer with recording of quality events and transients

,

Code:

    SPECIFICATIONS

    Auxiliary battery power supply
    Autonomy
    2 h (without 3G), 50 min (with 3G)
    Battery type
    Litio (3,7 Vc.c.)
    Capacity
    3700 mAh
    Load temperature
    0 … 40 °C
    Load time
    6 h
    AC power supply
    Installation category
    CAT II 300 V
    Consumption
    22…28 VA
    Frequency
    47…63 Hz
    Nominal voltage
    100…240 Vc.a.(Adaptador de alimentación de c.a.)
    Powered by charger, adapter
    Output voltage
    9 Vc.c.
    Maximum power
    18 W
    Battery specification
    Capacity
    220 mAh
    Performance-guarantee
    10 años
    Type
    Litio
    Voltage
    3 Vc.c.
    Specific technical characteristics of current sensors
    Linearity
    0,2 % (3…120 % In)
    Measurement range
    1…100 A
    Standards
    Certifications
    UL, CAN/CSA-C22.2 No. 61010-1, 3rd Edition, 2012-5, CE
    Electrical safety, Maximum height (m)
    2000
    Standards
    Recycling European Directive 2002/96/EC, EN 61326-1, UL 61010-1, 3rd Edition, 2012-05-11, IEC 61010-1, 3rd Edition
    Current measurement circuit
    Installation category
    CAT III 600 V
    Nominal current (In)
    Depending on the clamp
    Phase current measurement
    Transformadores con salida 0,250 A ó 0,333 V
    Phase current measuring range
    1…200 % In
    Maximum input current consumption
    0,0004 VA
    Maximum pulse current
    3 x In A
    Minimum current measurement
    Depending on the clamp
    Voltage measurement circuit
    Installation category
    CAT III 600 V
    Consumption
    0,15 VA
    Sampling frequency
    45…65 Hz
    Input impedance
    2,4 MΩ
    Voltage measuring range
    45…65 Hz
    Minimum measurement voltage (Vstart)
    10 V ac
    Communications
    Band
    2,4 GHz.
    Connection mechanism
    Wi-Fi
    Electrical safety
    Insulation
    Double-insulated electric shock protection class II (IEC 61010-1)
    Memory
    Write time
    1s, 1m, 5m, 15m, 1h, 1d
    Type
    FAT 32
    Measurement accuracy
    Current asymmetry (Ka)
    Class A (IEC 61000-4-30)
    Voltage asymmetry (Ka)
    Class A (IEC 61000-4-30)
    Current unbalance (Kd)
    Class A (IEC 61000-4-30)
    Voltage unbalance (Kd)
    Class A (IEC 61000-4-30)
    Frequency measurement
    Class 0,1 (45…65 Hz)
    Phase current measurement
    class 0,2 (1…200 % In) (IEC 61557-12)
    Reactive energy measurement (kvarh)
    Class 1 (IEC 62053-23)
    Reactive power measurement (kvar)
    Class 1 ± 1 digit (IEC 61557-12) (Vn ac 230/110)
    Apparent power measurement (kVA)
    class 0,5 ± 1 digit (IEC 61557-12) (Vn ac 230/110)
    Active energy measurement (kWh)
    Class 0,5S (IEC 62053-22)
    Active power measurement (kW)
    class 0,5 ± 1 digit (IEC 61557-12) (Vn ac 230/110)
    Power factor measurement
    Class 0.5 (IEC 61557-12)
    Voltage THD
    Class 0.5 (IEC 61557-12)
    Phase voltage measurement
    Class 0.2 0,2 (10…1000 VF-N c.a.) (IEC 61557-12)
    Pinst. Flicker
    3 % (IEC 61000-4-15)
    Pst Flicker
    5 % (0,2 … 10Pst) (IEC 61000-4-15)
    Current harmonics (THD)
    (up 50th) Class 1 (IEC 61000-4-7)
    Voltage harmonics (THD)
    (up 50th) Class 1 (IEC 61000-4-7)

    DIMENSIÓN

    VÍDEOS

    DESCARGAS

    ACCESORIOS