Three-phase energy meters with PLC system (measuring, load profiling, multi configurable billing calendar)

410-QD1A-B0B10

410-QD1A-B0B10, Three-phase energy meters direct connection

Code: QB4N0

  • Type Consumer: 4
  • Discon. relay: No
  • Communications: RS-232 | PRIME
  • Nº relays: 0
  • Class (Active/Reactive): B (1) / 2
  • System: Three-phase
  • Measure: Direct
  • Measurement Range (V): 3x230/400
  • Measurement Range (A): 10 (100)
  • Quadrants: 4
  • Frequency (Hz): 50

INFORMATION

Description

The Cirwatt B 410DP is a digital multifunction three-phase class-B/Class-1 meter for active energy and Class-2 for reactive energy. This meter complies with the international IEC 62053-21 and IEC 62053-23 standards, and with the European regulations on energy meters, EN 50470-1 and EN 50470-3 (MID), which allows them to be installed in any European Union country.

It features PLC (Prime Line Carrier) PRIME communications via the electrical grid, as well as an optical port and an RS-232 port for remote management via a GSM/3G modem. Both communications use the DLMS protocol.
It also has a logger for up to 3 months of time records for the 6 types of energy. It also allows the data to be read in the absence of voltage.
It includes a circuit breaker, which allows the user to control the electricity demand, which can be managed remotely using PLC communications.

SPECIFICATIONS

AC power supply
Nominal voltage
3 x 230 (400) V
Frequency
50 / 60 Hz
Consumption
< 2 W; < 10 VA
Tolerance
80 % ... 115 % Un
Battery specification
Type
Lithium
Performance-guarantee
> 20 years @ 30 ºC
Memory
Type
Serial flash
Write time
90 days
Memory capacity
Data: non-volatile memory, Setup and events: serial-flash
Voltage measurement circuit
Nominal voltage
3x230/400 V
Consumption
< 2 W; 10 VA
Nominal frequency
50 / 60 Hz
Connection
Asymmetrical
Current measurement circuit
Maximum current
100 A
Minimum current measurement
< 0,5 x Itr
Reference current (Iref)
10 A
Consumption
< 0,1 VA
Measurement accuracy
Active energy measurement (kWh)
EN 50470 (Class B) IEC 62053-21 (Class 1)
Reactive energy measurement (kvarh)
IEC 62053-23 (Class 2)
Serial communication
Technology / Type
RS-232
Communication Network
Technology / Type
PRIME
User interface
Display type
LCD
Resolution of the display
up to 8 digits (8 mm)
Environmental characteristics
Working temperature
-40 ... +70 ºC
Storage temperature
-40 ... +85 ºC
Relative humidity (without condensation)
95 % max.
Mechanical characteristics
Envelope
DIN 43859
Weight (kg)
1,6
Size (mm) width x height x depth
172 x 255 x 67 (mm)
Features / performance
Billing closures
12 locks per contract. Programable date and hour
Load curve
1 load curves, programmable integration time (1 … 60 min)
Tariff programming
12 days 24 types of data 6 types of tariffs 30 public holidays
Clock
Type
Gregorian calendar
Source
Temperature compensated oscillator
Accuracy (EN 61038)
< 0,5 s/day (23 ºC)
PLC
Modulation system
OFDM
Hardware
CENELEC
Protocol
DLMS / PRIME
Optical communication interface
Type
Serial;bi-directional
Hardware
IEC 62056-21
Protocol
DLMS

DIMENSIONS

CONNECTIONS

VIDEOS

DOWNLOADS

Diagram connection
Datasheet

ACCESORIES

TAMBIÉN TE PUEDE INTERESAR