Three-phase current transformers for energy meters

TRMC-X3 200/5 Ext

TRMC-X3 200/5 Ext, Current transformers

Code: Q301T2010E000

  • Usefull diam.(mm): 38
  • Cable (m): 7
  • Class 0,5S Power (VA): 2,5
  • Measurement Range (A): 200/5

SPECIFICATIONS

AC power supply
Frequency
50 / 60 Hz
Electrical characteristics
Safety factor (SF)
5
Power
2,5 … 5 VA
Insulation voltage, circuit
3 kV
Mechanical characteristics
Size (mm) width x height x depth
245 x 80 x 98.5 (mm)
Envelope
Self-extinguishing V0 plastic, filled with synthetic resin
Cable gauge at input and output terminals
1,5 mm2
Connection type
Three-phase busbar, cable length 1.5 m
Weight (kg)
2,9
Environmental characteristics
Thermal Class
class B (+130 ºC)
Relative humidity (without condensation)
5 … 95 %
Storage temperature
-15 … +50 ºC
Working temperature
-5 … +40 ºC
Specific technical characteristics of current sensors
Operating voltage
0,72 kV~ máx.
Standards
Certifications
UL 94
Electrical safety, Maximum height (m)
1000
Standards
IEC 61869-2, IEC 60038, IEC 60071-1, IEC 60071-2, IEC 60721-3-3, IEC 60085, EN 60076-5, UNE 21-305-90, UNE-EN 60695-2-10, UNE-EN 60695-2-11, UL 94
Current measurement circuit
Primary current measurement
200 A
Dynamic current (Idyn)
2,5 Ith
Thermal short-circuit current (Ith)
60 In
Transformation ratio
… / 5 A

DIMENSIÓN

VÍDEOS

DESCARGAS

Technical guide
Dimensions
Diagram connection
Datasheet
CE-certified

ACCESORIOS