SPECIFICATIONS

AC power supply
Nominal voltage
100…240 Vc.a.(Adaptador de alimentación de c.a.)
Frequency
47…63 Hz
Consumption
22…28 VA
Installation category
CAT II 300 V
Auxiliary battery power supply
Battery type
Litio (3,7 Vc.c.)
Capacity
3700 mAh
Load time
6 h
Load temperature
0 … 40 °C
Autonomy
2 h (without 3G), 50 min (with 3G)
Powered by charger, adapter
Output voltage
9 Vc.c.
Maximum power
18 W
Battery specification
Type
Litio
Voltage
3 Vc.c.
Performance-guarantee
10 años
Capacity
220 mAh
Memory
Type
FAT 32
Write time
1s, 1m, 5m, 15m, 1h, 1d
Voltage measurement circuit
Voltage measuring range
10 … 600 V~ (Ph-N)
Frequency measuring range
42,5 … 69 Hz
Input impedance
2,4 MΩ
Minimum measurement voltage (Vstart)
10 V ac
Consumption
0,15 VA
Installation category
CAT III 600 V
Sampling frequency
45…65 Hz
Current measurement circuit
Nominal current (In)
Depending on the clamp
Phase current measurement
Transformadores con salida 0,250 A ó 0,333 V
Phase current measuring range
1…200 % In
Maximum pulse current
3 x In A
Minimum current measurement
Depending on the clamp
Maximum input current consumption
0,0004 VA
Installation category
CAT III 600 V
Specific technical characteristics of current sensors
Measurement range
100/1000/10000 A
Linearity
2 % (10…200 % In)
Measurement accuracy
Phase voltage measurement
Class 0,2 (10…600 VPh-N ~) (IEC 61557-12)
Phase current measurement
class 0,2 (1…200 % In) (IEC 61557-12)
Frequency measurement
Class A ( 42.5 ... 69 Hz) (IEC 61000-4-30)
Active power measurement (kW)
class 0,5 ± 1 digit (IEC 61557-12) (Vn ac 230/110)
Apparent power measurement (kVA)
class 0,5 ± 1 digit (IEC 61557-12) (Vn ac 230/110)
Reactive power measurement (kvar)
Class 1 ± 1 digit (IEC 61557-12) (Vn ac 230/110)
Active energy measurement (kWh)
Class 0,5S (IEC 62053-22)
Reactive energy measurement (kvarh)
Class 1 (IEC 62053-23)
Power factor measurement
Class 0.5 (IEC 61557-12)
Voltage THD
Class 0.5 (IEC 61557-12)
Voltage harmonics (THD)
(up 50th) Class 1 (IEC 61000-4-7)
Current harmonics (THD)
(up 50th) Class 1 (IEC 61000-4-7)
Pinst. Flicker
3 % (IEC 61000-4-15)
Pst Flicker
5 % (0,2 … 10Pst) (IEC 61000-4-15)
Voltage unbalance (Kd)
Class A (IEC 61000-4-30)
Voltage asymmetry (Ka)
Class A (IEC 61000-4-30)
Current unbalance (Kd)
Class A (IEC 61000-4-30)
Current asymmetry (Ka)
Class A (IEC 61000-4-30)
Wireless communication
Technology / Type
Wi-Fi
Band
2,4 GHz.
Standards
Standards
Recycling European Directive 2002/96/EC, EN 61326-1, IEC 61010-1, 3rd Edition
Certifications
CE
Electrical safety, Maximum height (m)
2000
Electrical safety
Insulation
Double-insulated electric shock protection class II (IEC 61010-1)