Power quality analyzers

CVM-A1500-ITF-485-ICT2

CVM-A1500-ITF-485-ICT2, Power quality analyzers with recording of quality events and transients in accordance with (IEC 61000-4-30 Ed.2) Class A

Code: M56311.

  • Protocol: Modbus/RTU | BACnet | webserver (HTTP) | XML | HTML5
  • Memory: 200 MB
  • Memory: Yes
  • Events / Waveform: Yes
  • Certification: -
  • Energy accuracy: 0,2S (.../5A)
  • Communications: RS-485 | Ethernet
  • Transistor output: 2
  • Nº relays: 2
  • Digital inputs: 2
  • Harmonics: 63
  • Input current: .../5 A | .../1 A | 250 mA
  • Mounting: Pannel
  • Modules: 144 x 144

INFORMATION

Description

CVM-A1500 is a panel mounted power quality analyzer with EMS (Energy Management Software) integrated. Its internal Web Server (html5) allows any user to have full installation control by using any web browser.

Designed to be installed in the most relevant or critical part of electric installations since it registers and monitors a wide range of variables (almost one year of data with RMS, maximum and minimum values). The device also registers power quality events such as swells, dips, interruptions (every half cycle) and transients (according to IEC 61000-4-30 Class A). Any event will be immediately captured with the voltage and current waveform.

This model adds the measurement of power quality variables (defined in the standard EN 50160) such as flicker, unbalance (Kd) and asymmetry (Ka) coefficients or voltage and current harmonics decomposition up to 63th.  In addition it is possible to monitor in real time the instantaneous waveforms of voltage and current through its oscilloscope function.

As an added value, CVM-A1500 displays the number of events and transients on each affected phase with the level reached, duration and its associated waveform. In addition, those events are directly displayed in CBEMA, ITIC y SEMI-F47 graphs.

The smart design of the CVM-A1500 allows users to customize their own screens in order to access to the information faster and easy. Remark that the device allows the connection though PowerStudio software to save and store, in a redundant way, all the information in a server or PC avoiding memory limits.

  • Dimensions:144 x 144 mm
  • Energy Management Software (EMS) included with historical data register
  • Register of power quality events, waveforms and instantaneous parameters.
  • Expandable up to 3 modules (inputs/outputs and communications)
  • VGA color display with high definition
  • IP 65 with airtight seal
  • 5 voltage channels + 4 ITF current channels
  • Active energy class 0,2S (IEC 62053-22)
  • Universal switching power supply AC/DC or DC
  • Ethernet communications (Web Server) + RS-485 (ModBus RTU or BACnet protocol)
  • 5 user customizable screens
  • 3 tariffs (selectable by digital input or by communications)
  • Cost calculation(any currency) and emissions of kgCO2
  • 2 relay outputs for alarms + 2 transistor outputs for alarms or pulses + 2 digital inputs to select tariff, to control logical states or pulse centralizer from any external meter.

Applications

  • Control, monitoring and logging of the power quality in High and Low Voltage distribution panels. Performed directly or remotely thanks to its WEB server. Integration in SCADA systems through XML requests.
  • 4 alarms (2 per transistor and 2 per relay), fully and independently programmable according to a low or high value, hysteresis, connection/disconnection delays, normally open or closed standby status and interlocking.
  • Generation of impulses with transistor outputs, fully and independently configurable over any incremental parameter (energy, costs, kgCO2, total meter or tariff hours).
  • Transducer converting analogue signals to any instantaneous parameter measured or calculated by the unit, with built-in expansion modules with analogue outputs.
  • Display of process signals featuring a built-in expansion module with analogue inputs, with optional reporting of these signals to SCADA systems through communications systems.
  • Control of electrical load or alarm signal operations by programming the transistor or relay outputs that are built-in or added through expansion modules.
  • Datalogger integrated with Web server and XML (log of historical data).

SPECIFICATIONS

AC power supply
Nominal voltage
100…240 V ~
Frequency
45 ... 65Hz
Consumption
máx. 29.4 VA
Installation category
CAT III 300 V
DC power supply
Nominal voltage
120 … 300 Vdc
Consumption
max. 11.9 W
Installation category
CAT III 300 V
Voltage measurement circuit
Frequency measuring range
40…70 Hz
Input impedance
1.2MΩ
Minimum measurement voltage (Vstart)
10 V~
Installation category
CAT III 600V
Maximum input voltage consumption
0,15 VA
Current measurement circuit
Nominal current (In)
…/5A, …/1A, …/0.250A
Phase current measuring range
0.01…10A (…/5A),0.01…2A (…/1A), 0.01…0.5A (…/0.250A)
Neutral current measuring range
0.02...0.5A (.../0.250A, calculated)
Maximum pulse current
100 A
Minimum current measurement
0,01 A (…/5A, …/1A, …/0,250A
Maximum input current consumption
0,9 VA
Installation category
CAT III 600 V
Measurement accuracy
Phase voltage measurement
Class 0.1 ±1 digit (50…600 Vca, …/5A, …/1A, …/0.250A)
Neutral voltage measurement
Class 0.5 ±1 digit (50…600 Vca, …/5A, …/1A, …/0.250A)
Phase current measurement
class 0,1 ±1 digit 0.05…8A (…/5A),0.01…1.2A ( …/1A), class 0,2 ±1 digit 0.01…0.3A (…/0.250A)
Neutral current measurement
class 1 ±1 digit 0,1...6A (…/5A),0.01…1.2A ( …/1A), calculated (…/0.250A)
Frequency measurement
Class 0.02 (…/5A, …/1A, …/0.250A)
Active power measurement (kW)
(Vn 230/110 Vac) class 0.5 ±1 digit 0.05…6A (…/5A),0.01…1.2A ( …/1A), 0.01…0.3A (…/0.250A)
Apparent power measurement (kVA)
(Vn 230/110 Vac) class 0.5 ±1 digit 0.05…6A (…/5A),0.01…1.2A ( …/1A), 0.01…0.3A (…/0.250A)
Reactive power measurement (kvar)
(Vn 230/110 Vac) Class 1 ±1 digit 0.05…6A (…/5A),0.01…1.2A ( …/1A), 0.01…0.3A (…/0.250A)
Active energy measurement (kWh)
(IEC 62053-22) Class 0.2S (…/5A), Class 0.5S (…/1A), Class 0.5S (…/0.250A)
Reactive energy measurement (kvarh)
(IEC 62053-23) Class 1 (…/5A), Class 2 (…/1A, …/0.250A)
Power factor measurement
class 0,5 (…/5A, …/1A, …/0.250A)
Voltage THD
class 1 (…/5A, …/1A, …/0.250A)
Voltage harmonics (THD)
class 1 (…/5A, …/1A, …/0.250A)
Current THD
class 1 (…/5A, …/1A, …/0.250A)
Current harmonics (THD)
class 1 (…/5A, …/1A, …/0.250A)
Pinst. Flicker
3 % (IEC 61000-4-15)
Pst Flicker
5 % (0,2…10 Pst) (IEC 61000-4-15)
Voltage unbalance (Kd)
class A (IEC 61000-4-30)
Voltage asymmetry (Ka)
Class A (IEC 61000-4-30)
Current unbalance (Kd)
class A (IEC 61000-4-30)
Current asymmetry (Ka)
class A (IEC 61000-4-30)
Digital transistor outputs
Quantity
2
Maximum voltage
48 Vdc
Maximum current
130mA
Maximum frequency
1 kHz
Pulse width
1 ms
Pulse output, time period (Ton / Toff)
0,3 ms/0,7 ms
Digital relay outputs
Electrical life (at maximum load)
3x104 cycles
Mechanical life
1x107 cycles
Maximum switching capacity
1500 VA
Digital inputs
Quantity
2
Type
Potential-free contact
Input/output insulation
4 kV
Maximum short-circuit current
5 mA
Maximum open circuit voltage
15 Vdc
Serial communication
Technology / Type
RS-485 / BACnet
Protocol
ModBus/RTU, BACnet
User interface
Display type
TFT color
Resolution of the display
VGA (640x480)
LED
3 LED
Keyboard
Capacitive, 3 keys
Environmental characteristics
Working temperature
-10…+50 ºC
Storage temperature
-20… +80 ºC
Relative humidity (without condensation)
5 ... 95%
Protection class
IP 40 (Front), IP 65 (Sealing), IP 30 (unmounted)
Mechanical characteristics
Envelope
Self-extinguishing UL94-V0 plastic
Fastening
Pannel (DIN43700) 138x138
Weight (kg)
0,79
Size (mm) width x height x depth
144.7 x 144.7 x 131.1 (mm)
Standards
Standards
UNE EN 61010, UNE EN 61000-6-4, UNE EN 61000-6-2, IEC 664, UNE-EN 55022, Measures according to : IEC 61557-12
Certifications
UL/CSA 61010-1 3rd edition
Electrical safety, Maximum height (m)
2000

DIMENSIONS

CONNECTIONS

VIDEOS

DOWNLOADS

User's manual
Technical guide
3D
Dimensions
Diagram connection
Configuration guide
Datasheet
Presentation
Other Certificates
Software & Firmware
Catalogue
Leaflet

ACCESORIES