Measuring transducers

CV-A-RMS Out1

CV-A-RMS Out1, Transducer Vac

Code: M25051.

  • Output type: 1
  • Analog output: 0…20mA
  • Measure: 300 Vac
  • Paramètre: V ~

INFORMATION

Description

The CV-A transducers, convert A.C voltage to D.C process indicator signal.
The analog output is directly proportional to the input signal, calibrated as a RMS with sinus signal of 50 Hz.

SPECIFICATIONS

AC power supply
Nominal voltage
24/115/230/400 Vca (-15…+20%)
Frequency
40…90 Hz
Consumption
2,5 VA
AC power supply, insulation
Test voltage (kV)
3 kV RMS 50 Hz 1min
Pulse test (kV)
4 kV (1,2/50µs)
DC power supply
Nominal voltage
9…36 Vdc / 90…140 Vdc
Consumption
2,5 VA
DC power supply, insulation
Test voltage (kV)
2 kV RMS 50Hz 1 min
Pulse test (kV)
3 kV (1,2/50µs)
Voltage measurement circuit
Nominal voltage
0…300 Vca
Voltage measuring range
0…150 % Vn
Frequency measuring range
45…65 Hz
Input impedance
3000 Ω/V
Maximum permanent measurement voltage
1000 V
Measurement accuracy
Phase current measurement
0,2 % FS
Analogue outputs
Displaced output
0,2…2 V / 2…10 V / 4…20 mA
Current mode, nominal range
0…20 mA
Voltage mode: nominal output range
0…5, 10 Vac
Analogue inputs
Load impedance in voltage
> 500 Ω
Load impedance in current
< 500 Ω
Response time
< 300 ms (0…99 % Vn)
Ripple (effective RMS value)
< 0,5 %
Environmental characteristics
Working temperature
-10…+55 °C
Storage temperature
-40….+70 °C
Protection class
IP 20 (Terminals) IP 40 (case)
Standards
Standards
IEC 529, IEC 688, IEC 801, EN 50081-2, EN 50082-2, IEC 1010
Electrical safety, Maximum height (m)
2000
Mechanical characteristics
Weight (kg)
0,31
Size (mm) width x height x depth
40 x 72 x 110 (mm)

DIMENSIONS

CONNECTIONS

VIDEOS

DOWNLOADS

User's manual
Dimensions
Diagram connection
Datasheet

ACCESORIES