Automatic capacitor banks with detuned filters (contactors switching), type P=7% (fres=189 Hz), 50 Hz.

OPTIM FR4-P&P-200-440

OPTIM FR4-P&P-200-440, Detuned capacitor bank

Code: R54S28.

  • Cable section (mm2): 150
  • Nr steps: 3
  • kvar (400 V): 165
  • kvar (440 V): 200
  • Optional circuit breaker (A) : 400
  • Optional manual switch (A): 400
  • Composition: 50 + 50 + 100
  • Use voltage (V): 440

INFORMATION

Description

The OPTIM FR P&P Series capacitor banks with detuned filters have been designed for power compensation purposes in networks with fluctuating load levels, a high content of harmonics and where there is a risk of resonance. Power variations are relatively slow (in seconds) so that the switching operations are carried out with contactors.

Applications

Its application is mainly focused on the compensation of installations with different loads, which require a regulated compensation, as a result of the power factor variations and where there is a high content of harmonics in the network.

  • Fixed detuned filters. For the compensation of transformers and motors (OPTIM FRF / FRM)
  • Automatic detuned filters, For the monitoring of variable loads (OPTIM FR P&P).

SPECIFICATIONS

Electrical characteristics
Voltage
400 V (50 Hz) (other voltages on request)
Reinforcement voltage
440 V
Surge
10 % 8 h over 24 h 15 % up to 15 min over 24 hours 20 % up to 5 min over 24 hours 30 % up to 1 min over 24 hours
Manoeuvre voltage
Contactors: 230 V
Discharge resistance
75 V / 3 min
Tolerance C
-5% / 10 %
Losses (W)
< 0,5 W/kvar
Current measurement circuit
Permanent overload
1,3 In
Transformation ratio
In / 5A
Environmental characteristics
Working temperature
Tª class D: Daily average: 45 ºC, annual average: 35 ºC, maximum: 55 ºC, minimum: -50 ºC
Relative humidity (without condensation)
80%
Protection class
IP 21
Mechanical characteristics
Envelope
Sheet metal RAL 7035 Grey / RAL 3005 Garnet
Fastening
Vertical / Self-supporting
Ventilation
Natural or forced according to options
Weight (kg)
209
Size (mm) width x height x depth
900 x 1900 x 650 (mm)
Protection
Element
Individual protection of each step with fuses with high rupture power (HRP). NH-00 Series.
Features / performance
Components
CLZ capacitor (460 V) Contactors with pre-insertion block and quick discharge resistor Two-pole protection circuit-breaker for capacitor bank and regulator operations. Power factor regulator of the Computer C Wi-Fi series. Detuned filters tuned at 189 Hz (50 Hz) /227 Hz (60 Hz) for the protection against harmonics present in the network and to avoid the problems of resonance with fifth or higher order harmonics. Built-in thermostat for the disconnection of the step in case of excessive temperatures (90 ºC). Auto-transformer.
Optional
Manual capacitor bank header switch Automatic capacitor bank header switch Automatic switch + Earth leakage protection at the capacitor bank’s header Forced ventilation unit + thermostat Polycarbonate plate to protect against direct contacts
Standards
Standards
IEC 60831-1, UNE 60831-1, IEC 61921, IEC 60439, IEC 61439
Electrical safety, Maximum height (m)
2000 m

DIMENSIONS

CONNECTIONS

VIDEOS

DOWNLOADS

User's manual
Dimensions
Diagram connection
Datasheet
CE-certified
Video Installation
Other Certificates
Software & Firmware
Catalogue
Leaflet

ACCESORIES