Power analyzer, panel mounted 96 x96

CVM-C11-ITF-IN-485-ICT2

CVM-C11-ITF-IN-485-ICT2, Power analyzer 96 x 96

Code: M58541.

  • Protocol: Modbus/RTU | BACnet
  • Communications: RS-485
  • Transistor output: 2
  • Nº relays: 2
  • Digital inputs: 2
  • Measuring Channels: 4
  • Harmonics: 31
  • Power supply: 100...270 Vac/dc
  • Input current: .../5 A | .../1 A
  • Mounting: Pannel
  • Modules: 96 x 96

INFORMATION

Description

The CVM-C11 is a power analyzer for a panel (96 x 96 mm) with power logging. Ideal for analyzing electrical and consumption quality variables, such as THD% for voltage and current, as well as individual harmonics for each phase up to the 31st. The inclusion of neutral current measurement lets users detect any imbalance, as well as detect overloads in the neutral conductor. Compact and versatile with measurements in 4 quadrants (consumption and generation), suitable for medium- and low-voltage installations.
Display and interface characteristics:

  • User-defined parameter display.
  • Backlit screen
  • On-screen graphic display of instantaneous active power
  • On-screen graphic display of all quadrants (Q1, Q2, Q3, Q4).
  • On-screen numerical indication of the value of cos φ or PF.
  • On-screen indication of the status of outputs, inputs and/or active tariff.
  • LED alarm indicator
  • Costs, kg of CO2 emitted and operating time per tariff

Applications

  • Discrimination of power consumption into three tariffs. Ideal for determining consumption during three different work shifts or from three different energy sources (grid, generator and photovoltaic generation), using the digital inputs.
  • Generation of an impulse signal related to cost, kg of CO2 emitted or proportional to energy consumption or generation.
  • Alarm control (2 relay outputs + 2 digital outputs) for any instantaneous parameter, whether measured or calculated. Adjustable based on maximum/minimum value, hysteresis (%), NO/NC, connection/disconnection delay and interlocks.

SPECIFICATIONS

AC power supply
Installation category
CAT III 300 V
Consumption
2 ... 5 VA
Frequency
50 ... 60 Hz
Nominal voltage
100 ... 270 V ~ ± 10%
DC power supply
Installation category
CAT III 300 V
Consumption
1.2 ... 2 W
Nominal voltage
100 ... 270 Vdc ± 10%
Mechanical characteristics
Size (mm) width x height x depth
96 x 96 x 67.2 (mm)
Envelope
Self-extinguishing V0 plastic
Fastening
Panel
Weight (kg)
0,353
Environmental characteristics
Protection class
IP 54 (Front), IK 08
Relative humidity (without condensation)
5 ... 95%
Storage temperature
-25 …+75 ºC
Working temperature
-25 …+70 ºC
Current measurement circuit
Installation category
CAT III 300 V
Nominal current (In)
.../5A , .../1 A
Phase current measuring range
1 ... 120% In
Maximum pulse current
100 A
Minimum current measurement
1 mA
Voltage measurement circuit
Installation category
CAT III 300 V
Frequency measuring range
45 ... 65 Hz
Voltage measuring range
5 ...120% Un
Nominal voltage
100 ... 300 V Ph-N, 520 V Ph-Ph
Minimum measurement voltage (Vstart)
10 V
Communications
Fieldbus (BACnet)
MS/TP
Fieldbus (ModBus)
RS-485 / RTU
Stop bits (BACnet)
1
Stop bits (ModBus)
1-2
Parity (BACnet)
non
Parity
non-pair-impar
Protocol
ModBus RTU / BACnet
Speed
9600-19200-38400 bps (ModBus RTU & BACnet)
Standards
Electrical safety, Maximum height (m)
2000
Electrical safety, Installation category
CAT III 300 V
Electrical safety, Contamination level/class
Pollution resistance 2
Standards
EN IEC 61326-1, EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6, EN 61000-4-8, EN 61000-4-11, EN 61010-2-030, EN IEC 61557-12
User interface
LED
2 LED
Keyboard
3 keys
Display type
LCD Custom COG
Digital inputs
Input/output insulation
2000 V
Quantity
2
Type
NPN
Digital relay outputs
Electrical life (at maximum load)
60x103 cycles
Mechanical life
10x106 cycles
Maximum switching capacity
625 VA / 75 W (AC1)
Digital transistor outputs
Pulse width
30 ms a 400 ms (Programmable)
Quantity
2
Type
NPN
Maximum frequency
16 imp / s
Maximum current
50 mA
Maximum voltage
24 Vdc
Measurement accuracy
Phase current measurement
0.2%
Reactive energy measurement (kvarh)
Class 1 (only for the analizer without current transformers), IEC 62053-24
Reactive power measurement (kvar)
1% ± 2 digit
Active energy measurement (kWh)
Class 0.5S (only for the analizer without current transformers), IEC 62053-22
Active power measurement (kW)
0.5% ± 2 digit
Phase voltage measurement
0.2%

DIMENSIONS

CONNECTIONS

VIDEOS

DOWNLOADS

User's manual
Technical guide
3D
Dimensions
Diagram connection
Datasheet
Catalogue
CE-certified
Leaflet
Other Certificates

ACCESORIES