Power analyzer, colour display, panel mounted

CVM-B100-ITF-485-ICT2

CVM-B100-ITF-485-ICT2, Power analyzer

Code: M56011.

  • Protocol: Modbus/RTU | BACnet
  • Energy accuracy: 0,5 S (.../5A)
  • Communications: RS-485
  • Transistor output: 2
  • Nº relays: 2
  • Digital inputs: 2
  • Input current: .../5 A | .../1 A | .../250 mA
  • Mounting: Pannel
  • Modules: 96 x 96

INFORMATION

Description

The CVM-B100 and CVM-B150 units are panel mounted three-phase power analyzers (dimensions: 96x96 and 144x144 mm, respectively). Both offer 4-quadrant measurement (consumption and generation). Suitable for Medium or Low voltage installations, in both 3 or 4-wire three-phase circuits, two-phase circuits with or without neutral, single-phase circuits or ARON connections.

The CVM-B100 and CVM-B150 high-performance units feature a measurement engine that allows the user to analyse many different electrical parameters, in addition to offering a large variety of optional expansion modules for the same unit.

Features:

  • Format: 96x96 (CVM B100) and 144x144 (CVM B150)
  • High-resolution VGA colour screen
  • IP 65 front panel protection (with sealing joint)
  • 5 voltage inputs (3 phases + neutral + earth) 1000 Vf-f
  • 4 Current inputs, ITF
  • Class 0.2 voltage and current accuracy
  • Class 0.5S energy accuracy
  • Expandable unit, up to 4 modules, combining digital and analogue outputs, Modbus/TCP, MBus, LonWorks, Profibus, XML/Web
  • Modular (optional addition of expansion modules)
  • Touch-sensitive movement buttons
  • Universal power supply source
  • RS485 communications port (Modbus/RTU and BACnet protocols)
  • Customisation of parameters to be displayed
  • Operating hour indicator for preventive maintenance.

Other features:

  • Innovative SCV interface (Slide, Choose & View) for versatile data display, enabling the customisation of the parameters displayed on the screen
  • Electrical parameters: instantaneous, maximum, minimum (with date and time) and demand
  • Incremental electrical parameters (energy), times, costs, emissions
  • 3 Tariffs (can be selected via the digital input or RS485 communications)
  • Capable of showing costs and kgCO2 emission sources on the screen, depending on the energy consumed or generated
  • 2 Relay outputs for alarms with delay, times, ON and OFF, etc.
  • 2 transistor outputs for alarms or impulse generation, with all the possible configuration parameters
  • 2 digital inputs, with control over the selection of the unit’s tariffs or configurable for monitoring purposes, with RS-485 Modbus communications, monitoring of logical states of other electromechanical units. (RCCBs, thermal-magnetic circuit breakers, etc.)

Applications

  • Control and monitoring of all electrical parameters measured in any electric distribution panel and low and high-voltage connection points.
  • 4 alarms (2 per transistor and 2 per relay), fully and independently programmable: low or high value, hysteresis, connection/disconnection delays, normally open or closed standby status and interlocking.
  • Generation of impulses with transistor outputs, fully and independently configurable over any incremental parameter (energy, costs, kgCO2, total meter or tariff hours)
  • Transducer that converts analogue signals to any instantaneous parameter that the unit can measure or calculate, with built-in expansion modules with analogue outputs.
  • Display of process signals, with a built-in expansion module with analogue inputs; optional reporting of these signals to SCADA systems through communication systems
  • Control of electrical load or alarm signal operations by programming the transistor or relay outputs that are built-in or added through expansion modules.
  • Autonomous datalogger with web server, connected to a M-CVMAB-Datalogger module. Enables direct monitoring of the historical data stored in the unit via a conventional web browser.

400 Hz Applications

CVM-B150 provides a version adapted to 400 Hz networks specially designed for applications such as:

  • Aeronautical
  • Astronautics
  • Naval
  • Military

SPECIFICATIONS

AC power supply
Installation category
CAT III 300 V
Consumption
máx. 23.9 VA
Frequency
45 ... 65Hz
Nominal voltage
100 ... 240 V ~
DC power supply
Installation category
CAT III 300 V
Consumption
max. 12.2 W
Nominal voltage
120 … 300 Vdc
Mechanical characteristics
Size (mm) width x height x depth
97 x 99 x 99 (mm)
Envelope
Self-extinguishing V0 plastic
Fastening
Panel 92x92
Weight (kg)
0,516
Environmental characteristics
Protection class
IP 40 (Front), IP 65 (Sealing), IP 30 (unmounted)
Relative humidity (without condensation)
5 ... 95%
Storage temperature
-20… +80 ºC
Working temperature
-10…+60 ºC
Standards
Certifications
UL 61010-1 3rd edition, CAN/CSA-C22.2 No.61010-1 3rd. edition 2012-05
Electrical safety, Maximum height (m)
2000
Standards
IEC 61010-1 (1rd. Edition), UNE-EN 61000-6-2, UNE-EN 61000-6-4, IEC 60664-1, IEC 61010-2-030 (First Edition). Measurement according to IEC 61557-12
Current measurement circuit
Installation category
CAT III 600 V
Nominal current (In)
…/5A, …/1A, …/0.250A
Phase current measuring range
0.01…10A (…/5A),0.01…2A (…/1A), 0.01…0.5A (…/0.250A)
Neutral current measuring range
0.02...0.5A (.../0.250A, calculated)
Maximum input current consumption
0,9 VA
Maximum pulse current
100 A
Minimum current measurement
0,01 A (…/5A, …/1A, …/0,250A
Voltage measurement circuit
Installation category
CAT III 600V
Input impedance
1.2MΩ
Frequency measuring range
40…70Hz
Voltage measuring range
40…70 Hz
Maximum input voltage consumption
0,15VA
Minimum measurement voltage (Vstart)
10 V~
Communications
Fieldbus (BACnet)
MS/TP
Fieldbus (ModBus)
RS-485 / RTU
Stop bits (BACnet)
1
Stop bits (ModBus)
1-2
Parity (BACnet)
non
Parity
non-pair-impar (Modbus)
Protocol
ModBus/BACnet
Speed
9600-19200-38400-57600-76800-115200
User interface
Display format
4:3
LED
3 LED (CPU-Keys-ALARM)
Resolution of the display
VGA (640x480)
Keyboard
Capacitive, 3 keys
Display type
TFT color
Visible display area size
3.5"
Digital inputs
Input/output insulation
4 kV
Quantity
2
Type
Potential-free contact
Maximum short-circuit current
5 mA
Maximum open circuit voltage
15 Vdc
Digital relay outputs
Electrical life (at maximum load)
3x104 cycles
Mechanical life
1x107 cycles
Maximum switching capacity
1500 VA
Digital transistor outputs
Pulse width
1 ms
Quantity
2
Type
NPN
Pulse output, time period (Ton / Toff)
0,3 ms/0,7 ms
Maximum frequency
1 kHz
Maximum current
130 mA
Maximum voltage
48 Vdc
Measurement accuracy
Frequency measurement
Class 0.1 (…/5A, …/1A, …/0.250A)
Phase current measurement
class 1 ±1 digit 0.05…6A (…/5A),0.01…1.2A ( …/1A), calculated (…/0.250A)
Neutral current measurement
class 1 ±1 digit 0.05…6A (…/5A),0.01…1.2A ( …/1A), calculated (…/0.250A)
Reactive energy measurement (kvarh)
(IEC 62053-23) Class 1 (…/5A), Class 2 (…/1A, …/0.250A)
Reactive power measurement (kvar)
(Vn 230/110 Vac) Class 1 ±1 digit 0.05…6A (…/5A),0.01…1.2A ( …/1A), 0.01…0.3A (…/0.250A)
Apparent power measurement (kVA)
(Vn 230/110 Vac) class 0.5 ±1 digit 0.05…6A (…/5A),0.01…1.2A ( …/1A), 0.01…0.3A (…/0.250A)
Active energy measurement (kWh)
(IEC 62053-22) Class 0.5S (…/5A), Class 1 (…/1A), Class 1 (…/0.250A)
Active power measurement (kW)
(Vn 230/110 Vac) class 0.5 ±1 digit 0.05…6A (…/5A),0.01…1.2A ( …/1A), 0.01…0.3A (…/0.250A)
Power factor measurement
class 0,5 (…/5A, …/1A, …/0.250A)
Current THD
class 1 (…/5A, …/1A, …/0.250A)
Voltage THD
class 1 (…/5A, …/1A, …/0.250A)
Phase voltage measurement
Class 0.5 ±1 digit (50…600 Vca, …/5A, …/1A, …/0.250A)
Neutral voltage measurement
Class 0.5 ±1 digit (50…600 Vca, …/5A, …/1A, …/0.250A)
Current harmonics (THD)
class 1 (…/5A, …/1A, …/0.250A)
Voltage harmonics (THD)
class 1 (…/5A, …/1A, …/0.250A)

DIMENSIONS

CONNECTIONS

VIDEOS

CVM-B100 / CVM-B150. Technologically advanced power analyzer

New power analyzers CVM-B100 / CVM-B150
(1/4) Programming CVM-B100 / CVM-B150: Basic analyzer programming
(2/4) Programming CVM-B100 / CVM-B150: Programming transformation ratios
(3/4) Programming CVM-B100 / CVM-B150: Parameter Settings
(4/4) Programming CVM-B100 / CVM-B150: Digital inputs and outputs

DOWNLOADS

User's manual
Technical guide
3D
Dimensions
Diagram connection
Datasheet
Catalogue
Presentation
CE-certified
Leaflet
Product video
Video Installation
Other Certificates
Software & Firmware

ACCESORIES