4G Modem, Line-EDS system expandable modules

Line-M-4IO-A

Line-M-4IO-A, Expansion modules

Code: M58E03.CONSULTAR DISPONIBILIDAD

  • Protocol: Modbus/RTU
  • Analogue Inputs: 4 (0/4 … 20 mA)
  • Communications: Bus-Line
  • Analog output: 4 (0/4 … 20 mA) |4 (0/2 … 10 Vdc)
  • Mounting: DIN rail

INFORMATION

Description

Module with 4 analogue inputs and outputs Can be used to integrate 0-4...20mA analogue signals from control devices and sensors. The module has outputs to replicate the signals recorded through its inputs or to convert the parameters measured by the Line system devices in analogue form, 0/4...20mA or 0/2...10V, for management through external devices.

The expansion modules of the Line range provide a simple way to extend the features of any version of line-EDS-Cloud, line-EDS-PS, or of the line-CVM-D32 network analyser.

The modules are connected laterally and are detected automatically when the lateral connection is made, which greatly simplifies the installation and configuration of the modules.

Applications

  • Expansion of inputs/outputs from line-CVM-D32 or line-EDS network analysers.
  • Convert any instantaneous parameter measured or calculated by the device into analogue signals by incorporating analogue output expansion modules.
  • Track the status of components in the installation by using the analogue inputs to the module.

SPECIFICATIONS

DC power supply
Consumption
max. 3 W
Voltage measurement circuit
Input impedance
150 Ω
Analogue outputs
Quantity
4
Maximum internal voltage
12 V
Linearity
< 1 %
DAC resolution
4096 points
Current mode, nominal range
0 … 20 mA / 4 … 20 mA
Current mode: maximum load resistance
300 Ω
Voltage mode: nominal output range
0 … 10 V
Voltage mode, minimum load resistance
5 kΩ
Accuracy
1 % (0 ... 20 mA / 0 ... 10 V)
Analogue inputs
Quantity
4
Measurement type
current
Nominal input range
0 … 20 mA / 4 … 20 mA (Programmable)
Accuracy
< 1 %
Input impedance
150 Ω
Maximum allowable neutral current
22 mAdc
User interface
LED
9 LED
Environmental characteristics
Working temperature
-10 … +50 ºC
Storage temperature
-20 … +70 ºC
Relative humidity (without condensation)
5 … 95%
Protection class
IP30, Front: IP40
Mechanical characteristics
Envelope
Self-extinguishing V0 plastic
Fastening
DIN rail (IEC 60715)
Weight (kg)
0,134
Size (mm) width x height x depth
52.5 x 108 x 70 (mm)
Standards
Standards
UNE-EN 61010-1, UNE-EN 61000-6-2, UNE-EN 61000-6-4
Electrical safety, Installation category
CAT III 300 V
Electrical safety, Maximum height (m)
2000

DIMENSIONS

CONNECTIONS

VIDEOS

DOWNLOADS

User's manual
Technical guide
3D
Diagram connection
Datasheet
CE-certified
Product video
Other Certificates
Catalogue
Leaflet

ACCESORIES