Three-phase current transformers

MC3 - 63 A

MC3 - 63 A, Three-phase current transformers

Code: M73121.

  • Inner diameter (mm): 7,1
  • System: Three-phase
  • Class 0,5 Power (VA): 0,1
  • Max. Current (A): 63
  • Transformer type: Closed core

INFORMATION

Description

Current transformers specifically designed to be installed above a switch:

  • Transformer range from 63 to 250 A
  • Secondary 250 mA
  • Compatible with CIRCUTOR’s MC range of products: CVM-MINI, CVM-NET, CVM-NET4, CVM-C, CVM-B, CDP-0, CDP-G

Applications

Installation in confined spaces, utilizing the space above the circuit breakers and earth leakage protection In installations that allow the power supply to be shut down for the installation of transformers.

SPECIFICATIONS

Electrical characteristics
Safety factor (SF)
FS 5
Power
0.1 VA (Class 0,5)
Insulation voltage between terminals S1-S2
3 kV
Mechanical characteristics
Size (mm) width x height x depth
59.7 x 24.7 x 31.7 (mm)
Envelope
Plastic V0 self-extinguishing
Weight (kg)
0,102
Environmental characteristics
Thermal Class
Class B (+130 ºC)
Protection class
IP 20
Specific technical characteristics of current sensors
Inner diameter Ø (mm)
7,1
Operating voltage
0,72 kV~ máx.
Current measurement circuit
Nominal frequency
50 / 60 Hz
Primary current measurement
63 A
Dynamic current (Idyn)
2,5 Ith
Thermal short-circuit current (Ith)
60 In
Transformation ratio
…/ 250 mA
Standards
Standards
IEC 60044-1
Measurement accuracy
Accuracy
Clase 0,5

DIMENSIÓN

VÍDEOS

DESCARGAS

3D
Dimensions
Diagram connection
Datasheet
CE-certified

ACCESORIOS

TAMBIÉN TE PUEDE INTERESAR