Residual current relay, type B

RGU-100B

RGU-100B, Residual current monitoring relay, type B

Code: P11961.

  • Protocol: Modbus/RTU
  • Módules: 3
  • Pre-alarm relay: Yes
  • Communications: RS-485
  • Nº relays: 1
  • IΔn (A): 0,03 … 3 A
  • Power supply (Vac): 230 Vac
  • Delay: 0,1 … 5 s, INS, SEL
  • Mounting: DIN rail

INFORMATION

Description

The residual current current intensity monitoring and protection relay (IEC 62020), compatible with the WGB series, for type B loads (IEC 60755).

High-performance relay with the following main features and functions:

  • Electronic relay with relay output.
  • Measures in alternating, continuous or mixed current (Type B according to IEC 60755).
  • It measures and displays the current intensity through the connection to the WGB-series residual current transformer.
  • Fully programmable with display showing instantaneous leakage current in real time on a high-contrast backlight display (display turns red when the relay trips).
  • Integrated RS-485 (Modbus) communications.
  • Pre-alarm relay.
  • Event log.
  • Remote control input.

Applications

Residual current protection or monitoring of single-phase or three-phase electrical loads in alternating current with continuous components, with frequencies up to 2 kHz, such as:

  • Variable speed drives.
  • UPS
  • Photovoltaic Installations.
  • Electric Vehicle Charging.
  • Active Filters.

SPECIFICATIONS

AC power supply
Nominal voltage
230 V~ (± 15 %)
Frequency
50 … 60 Hz
Consumption
7.5 VA
Installation category
CAT III 300 V
Digital transistor outputs
Type
Optocoupled
Maximum voltage
230 V ~
Maximum current
0.1 A
Digital relay outputs
Quantity
1
Maximum open contact voltage
230 V ~
Maximum current
6 A
Electrical life
60 × 103 (250 V ~ / 5A)
Mechanical life
10 x 106
Maximum switching capacity
1500 VA
Digital inputs
Type
Potential-free contact
Input/output insulation
5.3 kV
Input impedance
2 kΩ
Serial communication
Technology / Type
RS-485
Protocol
Modbus/RTU
User interface
Display type
LCD (negative)
LED
2
Keyboard
3 keys
Environmental characteristics
Working temperature
-10 … +50 ºC
Storage temperature
-20 … +70 ºC
Relative humidity (without condensation)
5 … 95 %
Protection class
IP 30, IP 40 (Vorderseite)
Mechanical characteristics
Envelope
Self-extinguishing V0 plastic
Weight (kg)
0,188
Size (mm) width x height x depth
52.5 x 118 x 74 (mm)
Differential protection
Transformer
External, WGB series (not included)
Type
Type B
Sensitivity (I∆n), A
0,03 … 3
Delay time (t∆)
INS - [S]-0.1-0.2-0.3-0.4-0.5-0.8-1-3-5 s
Standards
Standards
IEC 60947-2-M, Measurement conditions for type B waveforms specified in IEC 60755, UNE-EN 60068-2-1, UNE-EN60068-2-2, UNE-EN 60068-2-78
Electrical safety, Maximum height (m)
2000

DIMENSIONS

CONNECTIONS

VIDEOS

DOWNLOADS

User's manual
Technical guide
3D
Dimensions
Diagram connection
Datasheet
CE-certified
Other Certificates

ACCESORIES