Residual current relay, type A, for ultra-immunised WGC Transformer, 3 modules with display and programmable pre-alarm output.

RGU-10A

RGU-10A, Residual current relay for WGC Transformer, ultraimmunized type A, 3 modules and screen

Code: P11A70.

  • Módules: 3
  • Pre-alarm relay: Yes
  • Nº relays: 2
  • IΔn (A): 0,03 …30 A
  • Power supply: 110 ... 230 Vac
  • Delay: 0,1… 5 s, INS, SEL
  • Mounting: DIN rail

INFORMATION

Description

The RGU-10A is a type-A ultraimmunized earth leakage protection and monitoring relay that is compatible with the earth leakage transformers in the WGC range.
The device measures, calculates and displays the true RMS value of the residual current by using a residual current input from an external measurement toroidal transformer in the WGC series. 

The RGU-10A can be used to program and adjust all the parameters required to obtain complete protection and control of the installation. 

Main characteristics:

  • True root mean square value
  • RCM & MRCD on one device
  • Keypad locking of programming menu
  • RGB backlit display
  • Ultra-immunized type A RCD
  • Immunity to transients
  • Filtering of the highest order high frequencies
  • Trip adjustment between 80 and 100% IΔn
  • Inverse curve

Applications

The RGU-10A offers smart residual current protection.

Thanks to its design characteristics, this device provides the most complete type-A protection to ensure the safety of people and continuity of supply in electrical installations.

Its ultraimmunized system guarantees that a trip will only occur when it is absolutely necessary, avoiding financial losses due to unwanted trips.

Being able to view the instantaneous leakage value on the display, together with the pre-alarm indications, provides information on the status of the lines they protect so that proper preventive maintenance can be done.

SPECIFICATIONS

AC power supply
Nominal voltage
110 ... 230 V~
Frequency
50 … 60 Hz
Consumption
6.5 VA
External reset input for tripping
Type
Voltage 110 ... 230 V ~
Digital relay outputs
Quantity
2
Maximum current
6 A ~
Mechanical life
10 x 106
Maximum switching capacity
1500 VA
User interface
Display type
LCD custom (negative)
LED
2
Keyboard
3 keys
Environmental characteristics
Working temperature
-10 … +60 ºC
Storage temperature
-20 … +70 ºC
Relative humidity (without condensation)
5 … 95 %
Protection class
IP 30 (terminals), IP 40 (front)
Mechanical characteristics
Envelope
Sel-extinguishing V0 plastic
Fastening
DIN rail
Weight (kg)
0,186
Size (mm) width x height x depth
52.5 x 118 x 74 (mm)
Differential protection
Transformer
External, WGC series
Type
Type A ultra-immunised
Sensitivity (I∆n), A
0.03 - 0.1 - 0.2. - 0.3 - 0.5 - 0.75 - 1 - 1.5 - 2 - 3 - 5 - 10 - 30 A
Delay time (t∆)
INS - [S]-0.1-0.2-0.3-0.4-0.5-0.8-1-3-5 s
Standards
Standards
IEC60947-2-M
Electrical safety, Installation category
CAT III 300V ca
Electrical safety, Contamination level/class
2
Electrical safety, Maximum height (m)
2000

DIMENSIONS

CONNECTIONS

VIDEOS

DOWNLOADS

User's manual
Technical guide
3D
Dimensions
Diagram connection
Datasheet
CE-certified
Other Certificates
Catalogue
Leaflet

ACCESORIES