4 channels residual current relays, type A, 3 modules with display and a configurable prealarm output.

CBS-4C

CBS-4C, Station with 4 programmable residual current relays, type A

Code: P12712.

  • Protocol: Modbus/RTU
  • Módules: 3
  • Pre-alarm relay: Yes
  • Communications: RS-485
  • Nº relays: 4
  • IΔn (A): 0,03 …30 A
  • Power supply (Vac): 230 Vac
  • Delay: 0,02 … 10 s, INS, SEL
  • Mounting: DIN rail

INFORMATION

Description

  • Unit equivalent to 4 residual current protection networks. Features 4 independent programmable relays.
  • Four inputs for connecting the external toroidal transformers of the WGC / WGS series.
  • Super-immunised type-A relay with high-frequency current filtering and high immunity. True root mean square (TRMS) measure
  • Compact size: 3 modules
  • Features 5 independent programmable outputs (4 residual current tripping relays and 1 prealarm relay).

Applications

The CBS-4 multipoint residual current system associated with the WGC / WGS transformers offers smart residual current protection. Its design features guarantee maximum security and electrical service continuity, avoiding unwanted tripping. Viewing the instantaneous leakage value on the display, together with the prealarm indicators, makes it possible to obtain information on the status of lines to be protected, and to perform adequate preventive maintenance.
In addition, version CBS-4 C features RS-485 communications and, with the PowerStudio software, offers centralised supervision in real time, as well as keeping a log of historical data for future analysis.

SPECIFICATIONS

AC power supply
Nominal voltage
110 - 230 V~ (± 20 %)
Frequency
50/60 Hz
Consumption
6 VA
External reset input for tripping
Maximum voltage
230 Vca
Type
Optocoupled
Maximum power
0,7 W
Varistor characteristics
Maximum voltage
275 Vca
Characteristics solid state contact for pre-alarm
Max. power consumption 230 Vac : 5 VA / Umax. 275 Vac
Digital relay outputs
Nominal voltage
250 V ~
Nominal current
6 A ~
Maximum current
10 A ~
Nominal load in AC1
1500 VA
Mechanical life
10 x 106
Serial communication
Technology / Type
RS-485
Protocol
Modbus/RTU
Environmental characteristics
Working temperature
-10 … +50 ºC
Ambient temperature
-40 … +85 ºC
Relative humidity (without condensation)
5 … 95 %
Protection class
IP 20 (terminals), IP 41 (rear panel)
Mechanical characteristics
Fastening
DIN rail
Weight (kg)
0,28
Size (mm) width x height x depth
52.5 x 85 x 67.9 (mm)
Protection
Circuit breaker type
Contactor or Circuit Breaker + trigger coil
LED indication
Power supply voltageEarth leakage trippingPrealarm
Measure
True root mean square (TRMS)
Differential protection
Transformer
External, WG / WGC series
Type
Type A ultra-immunised
Sensitivity (I∆n), A
0,03 … 30
Delay time (t∆)
Programmable: 0.02 ... 10sInverse curve: Instantaneous or selective
Standards
Standards
IEC 60947, IEC 60755, IEC 62020, IEC 61008
Electrical safety, Installation category
CAT III 300V ca
Electrical safety, Maximum height (m)
2000
Electrical safety
Insulation
Double-insulated electric shock protection class II (IEC 61010-1)

DIMENSIONS

CONNECTIONS

VIDEOS

DOWNLOADS

User's manual
Technical guide
3D
Diagram connection
Datasheet
CE-certified
Catalogue
Leaflet

ACCESORIES