Motorized circuit breakers for overcurrent and residual current protection with reclosing by residual current relay

MCB.P C-2p-20A

MCB.P C-2p-20A, Circuit breaker

Code: P20214.

  • Poles: 2
  • In (A): 20 A
  • Curve: C

INFORMATION

Description

MCB-P or MCB-T are circuit-breakers that combine the functions of a circuit breaker (overload and short-circuit protection) and those of a contactor on the same element. There are two options with MCB:

  • Closed circuit-breaker: Allows remote control functions (contactor function). It can be disconnected and reconnected electrically with the adequate signal.
  • Circuit-breaker opened by an overload or short-circuit trip or by manual disconnection: remote control reset is not allowed, only manually.

The remote control function works on the same contacts as those of the circuit breaker, guaranteeing the disconnection in each case. The MCB-T type includes a remote control module with two auxiliary, potential free (three-wire) contacts that indicate the status of the MCB at the input of the remote control (contactor function) and/or the circuit breaker.

Applications

MCB are the perfect elements to guarantee self-reclosing residual current and overload protection applications, connected to WRKRT-25 relays.

SPECIFICATIONS

AC power supply
Frequency
50 / 60 Hz.
Digital relay outputs
Maximum open contact voltage
230 V ~
Maximum current
0,5 A
Mechanical life
> 20000 operations
Environmental characteristics
Protection class
IP 20 (according to DIN40050)
Differential protection
Sensitivity (I∆n), A
20
Thermal-magnetic protection
Nominal voltage
210 / 240 V ~
Trip curve, Type
C
Mechanical characteristics
Weight (kg)
0,81
Size (mm) width x height x depth
54 x 90 x 68 (mm)

DIMENSIONS

CONNECTIONS

VIDEOS

DOWNLOADS

User's manual
Datasheet

ACCESORIES