Self-reclosing residual current relay with power analyzer functions, transformers included

RECmax-CVM 4P D4-40

RECmax-CVM 4P D4-40, Self-reclosing residual current relay with power analyzer functions, 4-pole D-curve

Code: P2B146.

  • Poles: 4
  • In (A): 40 A
  • Breaking element: built-in
  • Curve: D

INFORMATION

Description

Self-resettable cut-off device with ultra-immunised circuit breaker and residual current protection and built-in power analyzer. Programmable unit with display, which measures leakage currents (residual current protection) and orders the disconnection or reclosing of the circuit breaker (circuit breaker protection) using an engine that regulates it mechanically. The measurement of leakage currents, IΔn, requires an external residual current transformer of the WGC type, which comes in the kit. It also has a built-in power analyzer that enables monitoring of up to 19 electrical parameters using the display or the built-in communications, with voltage measurement built into the unit and current measurement through the use of an external MC1 (for 2 poles) or MC3 (for 4 poles) current transformer, which comes in the kit.
This system is commonly used in single-phase and three-phase electrical installations that require a highly continuous electric supply. It has inputs/outputs that allow users to have information about and control of the status of the electrical installation where it is working. LED display and backlit (LCD) display:

  • Overcurrent and residual current protection and reclosing
  • Trip current intensity of the protection.
  • Number of reclosings
  • Protection status messages.
  • Measurement of electrical values (voltage, current, active power, cos φ) (other values via communications).

Applications

The RECmaxCVM kit ensures circuit breaker and residual current protection with automatic reclosing by default after a differential relay, overload or short-circuit trip. It also measures the electrical parameters of the circuit it protects. It is a very suitable solution for infrastructures located in areas that make it difficult to control and monitor. It can be installed in the electric panels of:

  • Telephone systems
  • TDT systems
  • Information systems, UPS systems

SPECIFICATIONS

AC power supply
Nominal voltage
230V ~ ± 20% (L1-N)
Frequency
50 / 60 Hz.
Consumption
7 VA
Installation category
CAT III 300 V
Electrical characteristics
Earthing system
TT - TN
Voltage measurement circuit
Nominal voltage
230 V ~ ±20 %
Frequency measuring range
50/60 Hz
Input impedance
400 kΩ
Installation category
CAT III 600 V
Sampling frequency
50/60 Hz
Current measurement circuit
Nominal current (In)
… / 250 mA
Phase current measuring range
1 … 100 % In
Minimum current measurement
0,2 % In
Installation category
CAT III 300 V~
Measurement accuracy
Phase voltage measurement
0,5 % ± 1 digit
Phase current measurement
5 % (for IN > 10% F.E.), value calculated from the vector sum measured in the phase currents.
Active power measurement (kW)
1% ±2 digits
Reactive power measurement (kvar)
2 % ±2 digit
Active energy measurement (kWh)
1%
Reactive energy measurement (kvarh)
2%
Serial communication
Technology / Type
RS-485
Protocol
Modbus/RTU
User interface
Display type
LCD
LED
2 LED
Keyboard
3 keys
Environmental characteristics
Working temperature
-10 … +55 ºC
Storage temperature
-30 … +70 ºC
Relative humidity (without condensation)
5 … 95 %
Protection class
IP 20
Mechanical characteristics
Envelope
Plastic V0
Fastening
DIN rail
Weight (kg)
0,78
Size (mm) width x height x depth
133 x 111.5 x 82 (mm)
Differential protection
Transformer
External, WGC-20SC series
Sensitivity (I∆n), A
0,03 - 0,1 - 0,3 - 0,5 - 1 A (programable)
Delay time (t∆)
Programmable trip delay (IEC 60947-2-M)
Thermal-magnetic protection
V~ Breaking capacity (IEC 60947-2)
415 V ~
Voltage breaking capacity (IEC 60898)
230 / 400 V ~
Rated short-circuit breaking capacity (Icn) / service short-circuit breaking capacity (Ics) (IEC 60898)
6 kA
Nominal voltage
240 / 415 V ~
Nominal current In (A)
40
Trip curve, Type
D
AC ultimate short-circuit breaking capacity (Icu) (IEC 60947-2)
10 kA
Standards
Standards
IEC TR 60755, IEC 60898-1, DIN EN 50022, IEC 60947-2-M, IEC 61010-1-3ª Ed., IEC 61000-6-4, IEC 62053-21, IEC 62053-23, IEC 61557-12
Electrical safety, Maximum height (m)
2000

DIMENSIONS

CONNECTIONS

VIDEOS

DOWNLOADS

User's manual
Technical guide
3D
Diagram connection
Configuration guide
Datasheet
CE-certified
Product video
Catalogue
Leaflet

ACCESORIES

TAMBIÉN TE PUEDE INTERESAR