Full residual current and circuit breaker reclosing and protection unit, panel

WRGU-10MTT-C-2-63A

WRGU-10MTT-C-2-63A, Self reclosing

Code: P21818.

  • Poles: 2
  • In (A): 63 A
  • Breaking element: built-in
  • Curve: C

INFORMATION

Description

The WRGU-10 MTT compact assembly forms a self-reclosing circuit breaker (overload and short-circuit) and residual current protection system in single-phase or threephase electrical installations with a neutral of up to 63 A. The assembly is composed of the following elements:

  • Residual current relay for protection, with RGU-10 MTT self-reclosing function
  • MP-T series motorized circuit breaker as an overload and short-circuit protection element, and as a circuit breaker in residual current protection
  • WGC residual current transformer, residual current sensor for residual current protection
  • Remote switch, for resets and external manual reclosures

Applications

The WRGU-10 MTT groups can be used to make safety compatible with the continuity of the service in remote installations or installations with more complicated maintenance. They ensure residual current (mandatory) and circuit breaker protection, guaranteeing selfreclosing for either of the two reasons. It is a very good solution in installations in special locations that are hard to control and monitor: telephony installations, television repeaters, refrigerating chambers, etc.

  • Telephony systems
  • DTT systems
  • Industrial refrigerating chambers

SPECIFICATIONS

AC power supply
Consumption
6 VA
Frequency
50 Hz
auxiliary power supply mode
230 V ~
Nominal voltage
230 V ~ (± 20 %)
Mechanical characteristics
Size (mm) width x height x depth
225 x 205 x 110 (mm)
Envelope
Colour box RAL 7035
Cable length to be stripped (mm)
7 mm
Torque setting
0.5 … 0.6 Nm
Cable gauge at input and output terminals
0,5 … 2 mm2
Weight (kg)
4
Environmental characteristics
Storage temperature
Circuit breaker: -55 … +55 ºC
Working temperature
Circuit breaker and relay: -25 ... +55 ºC / Motor reconnection: -25 ... +70 ºC
External reset input for tripping
Type
ON-OFF Remote
Motor
On / off pulse time
Opening time: < 10 ms / Closing time: < 1000 ms
Nominal voltage
230 / 380 V ~
Standards
Standards
IEC 60947-2, IEC 60755, UNE-EN 55022, UNE-EN 55011, UNE-EN 55024 level 4, IEC 61000-4-11
Digital relay outputs
Nominal load in AC
2500 VA
Nominal current
5 A ~
Maximum current
10 A ~
Electrical life
Magnetotérmico: 10000 maniobras / Motor reconexión: >20000
Mechanical life
Magnetotérmico: >20000 operations
Measurement accuracy
Phase current measurement
± 20 %
Differential protection
Type
Type A ultra-immunised
Sensitivity (I∆n), A
0,03-0,1-0,3-0,5 (Setup)
Delay time (t∆)
Curve INS / SEL
Protection
LED indication
Voltage presence Earth leakage tripping Reclosure timing
Measure
True root mean square (TRMS)
Circuit breaker type
Motorised circuit breaker MP-T series
Thermal-magnetic protection
Trip curve, Type
C
Nominal current In (A)
63
Breaking capacity
10 kA (IEC 60898)
Nominal voltage
240 / 415 V ~
Reclosure type
Reclosure number
Differential (15) / Circuit breaker (2)
Reset time
Diff & Magneto: 15 min
Reclosure time
Differential: 20 s, 40 s, rest 3 min / Circuit breaker: 3 min

DIMENSIÓN

VÍDEOS

DESCARGAS

Datasheet

ACCESORIOS