Full residual current and circuit breaker reclosing and protection unit, panel

WRGU-10MTT-C-2-63A

WRGU-10MTT-C-2-63A, Self reclosing

Code: P21818.CONSULTAR DISPONIBILIDAD

  • Poles: 2
  • In (A): 63 A
  • Breaking element: built-in
  • Curve: C

INFORMATION

Description

The WRGU-10 MTT compact assembly forms a self-reclosing circuit breaker (overload and short-circuit) and residual current protection system in single-phase or threephase electrical installations with a neutral of up to 63 A. The assembly is composed of the following elements:

  • Residual current relay for protection, with RGU-10 MTT self-reclosing function
  • MP-T series motorized circuit breaker as an overload and short-circuit protection element, and as a circuit breaker in residual current protection
  • WGC residual current transformer, residual current sensor for residual current protection
  • Remote switch, for resets and external manual reclosures

Applications

The WRGU-10 MTT groups can be used to make safety compatible with the continuity of the service in remote installations or installations with more complicated maintenance. They ensure residual current (mandatory) and circuit breaker protection, guaranteeing selfreclosing for either of the two reasons. It is a very good solution in installations in special locations that are hard to control and monitor: telephony installations, television repeaters, refrigerating chambers, etc.

  • Telephony systems
  • DTT systems
  • Industrial refrigerating chambers

SPECIFICATIONS

AC power supply
Nominal voltage
230 V ~ (± 20 %)
Frequency
50 Hz
Consumption
6 VA
auxiliary power supply mode
230 V ~
External reset input for tripping
Type
ON-OFF Remote
Measurement accuracy
Phase current measurement
± 20 %
Digital relay outputs
Nominal current
5 A ~
Maximum current
10 A ~
Nominal load in AC
2500 VA
Electrical life
Magnetotérmico: 10000 maniobras / Motor reconexión: >20000
Mechanical life
Magnetotérmico: >20000 operations
Environmental characteristics
Working temperature
Circuit breaker and relay: -25 ... +55 ºC / Motor reconnection: -25 ... +70 ºC
Storage temperature
Circuit breaker: -55 … +55 ºC
Mechanical characteristics
Envelope
Colour box RAL 7035
Weight (kg)
4
Size (mm) width x height x depth
225 x 205 x 110 (mm)
Motor
Nominal voltage
230 / 380 V ~
On / off pulse time
Opening time: < 10 ms / Closing time: < 1000 ms
Protection
Circuit breaker type
Motorised circuit breaker MP-T series
LED indication
Voltage presence Earth leakage tripping Reclosure timing
Measure
True root mean square (TRMS)
Differential protection
Type
Type A ultra-immunised
Sensitivity (I∆n), A
0,03-0,1-0,3-0,5 (Setup)
Delay time (t∆)
Curve INS / SEL
Reclosure type
Reset time
Diff & Magneto: 15 min
Reclosure time
Differential: 20 s, 40 s, rest 3 min / Circuit breaker: 3 min
Reclosure number
Differential (15) / Circuit breaker (2)
Thermal-magnetic protection
Breaking capacity
10 kA (IEC 60898)
Nominal voltage
240 / 415 V ~
Nominal current In (A)
63
Trip curve, Type
C
Standards
Standards
IEC 60947-2, IEC 60755, UNE-EN 55022, UNE-EN 55011, UNE-EN 55024 level 4, IEC 61000-4-11

DIMENSIONS

CONNECTIONS

VIDEOS

DOWNLOADS

Datasheet

ACCESORIES