Transformer with built-in residual current relay, type A

WGBU-90-105

WGBU-90-105, Residual current Relay

Code: P16023.

  • Usefull diam.(mm): 105
  • IΔn (A): 0,03 … 3 A
  • Delay: 0,02...1 s
  • Mounting: Panel background

INFORMATION

Description

The WGBU Series is a compact residual current protection system. It is composed of a toroidal transformer with a built-in residual current relay.

  • Multi-range electronic relay
    • The sensitivity can be adjusted to 0.03 ... 3 A
    • Trigger delay of 0.02 ... 1 s, adjustable
  • Type A relay with high frequency current filtering and high immunity. Monitoring in true root mean square (TRMS).
  • LED indicators:
    • Grid connection LED
    • Pre-alarm and trigger LED: 1 flash every 2 s, leak between 25 and 50 % of the sensitivity selected; 1 flash every 1 s, leak between 50 and 75 % of the sensitivity selected; 1 flash every 0.5 s, leak exceeding 75 % of the sensitivity selected; permanently lit, trigger of the residual current protection.

Applications

The WGBU series offers a reliable residual current protection, with simpler cabling and savings in the assembly time. In addition, installation is very simple, thanks to its compact dimensions.

SPECIFICATIONS

AC power supply, insulation
Test voltage (kV)
2,5 kV ~
AC power supply
Frequency
50/60 Hz
Nominal voltage
110/230 V ~ ±20 %
Mechanical characteristics
Size (mm) width x height x depth
170 x 146 x 113 (mm)
Fastening
DIN rail
Weight (kg)
0,573
Environmental characteristics
Protection class
IP 20 (terminals), IP 41 (rear panel)
Working temperature
-10 … +50 ºC
Standards
Standards
IEC 1008, IEC 255-5, UNE 801-2, UNE 801-3, UNE 801-4, UNE 60730-1
Other digital relay outputs
Insulation voltage
250 V ~
Electrical life
2 x 105
Digital relay outputs
Nominal current
6 A ~
Nominal voltage
250 V ~
Resistive load (max.)
250 Vca / 8 Aca
Differential protection
Type
Type A ultra-immunised
Sensitivity (I∆n), A
0,03 … 3 (seleccionable)
Delay time (t∆)
0.02... 5 s (selectable)
Transformer
Built-in, WG series
Protection
LED indication
Power supply voltage Earth leakage tripping Prealarm
Measure
True root mean square (TRMS)
Circuit breaker type
Contactor or Circuit Breaker + trigger coil

DIMENSIÓN

VÍDEOS

DESCARGAS

User's manual
Dimensions
Diagram connection
Datasheet
Catalogue

ACCESORIOS