Modular energy storage system

BAS-S154-25

BAS-S154-25, Indoor energy storage solution

Code: EB2502.

  • Power (VA): 25 kVA
  • Rated capacity: 154 kWh
  • In (A): 37
  • Rated voltage (Vac): 400
  • Frequency (Hz): 50
  • Battery type: LFP
  • Protocol: Modbus TCP/IP

INFORMATION

Description

Modular indoor energy storage solution for connecting in parallel to the grid, LFP lithium technology  Initial capacity of 154 kWh and 25 kVA of power (up to 616 kWh and 400 kVA).

  • Standardized energy storage system, expandable up to 4 x 154 kWh in terms of exchanging both energy and power with the grid.
  • All-in-one AC-coupled plug & play solution.
  • Rated storage capacity of 154 kWh.
  • From one to sixteen three-phase next-generation 4Q inverters of 25 kVA, for a total of 400 kVA.
  • Lithium iron phosphate technology for maximum operational and fire prevention safety.
  • FLEPS, systems to maximise fire safety
  • All-in-one energy management system with cloud connection to monitor all the installed systems, and a reliable remote maintenance service.
  • Easier maintenance thanks to plug-in modules (battery modules, battery management system, inverter).
  • Additional UPS system for safe operation during power outages.
  • Certified as per the VDE AR-N 4105/4110 standard.
Applications

  • Electromobility
  • Agriculture
  • Industry
  • Tertiary sector
  • Reduction of spikes
  • Emergency power
  • Optimized self-supply
  • Flexibility market
  • Network services (voltage and frequency stabilization)

SPECIFICATIONS

Battery specification
Type
Lithium-Ionen (LiFePO4), prismatic
Performance-guarantee
10 years or 470000 kWh of energy through the battery
Useful life
15 years(años) > 693000 kWh (90% DoD) > 900000 kWh (70% DoD) > 1100000 kWh (50% DoD)
Capacity
154 kWh
Electrical characteristics
Power
25 kVA
Nominal energy
154 kWh
Usable energy
138,6 kWh (90 % DoD)
Frequency
50 Hz
Nominal current In (A)
37
Surge protection (DSP)
Class 1 & 2
Earthing system
TN-S, TN-C-S, TT
Environmental characteristics
Ambient temperature
0 … + 55 ºC
Relative humidity (without condensation)
5 … 95 %
Protection class
IP 11
Installation, location, position.
The room height min. 2.5m. A minimum width of 1.5 m must be maintained in order to allow access for maintenance work.
Standards
Standards
UNE-EN 61000-6-2, UNE-EN 61000-6-4, UNE-EN 61439-1, UNE-EN 61439-2, UNE-EN 62109-1, UNE-EN 62619, UN 38.3, VDE-AR-E 2510-50 (6.2.6), VDE-AR-N 4105, VDE-AR-N 4110, UNE-EN 50549-1, TOR Producer Typ A, 2014/53/EU (RED), 2014/30/EU (EMC), 2014/35/EU (LVD), 2006/66/E6 (Bat. directives), UNE 217002, UNE 206007-1, UNE 206006
Electrical safety, Maximum height (m)
2000
Mechanical characteristics
Weight (kg)
2748,5
Size (mm) width x height x depth
3000 x 2310 x 938 (mm)

DIMENSIONS

CONNECTIONS

VIDEOS

DOWNLOADS

Catalogue
Leaflet

ACCESORIES

TAMBIÉN TE PUEDE INTERESAR