Self-reclosing overcurrent and residual current protection

RRM-P

RRM-P, Self-reclosing Relay

Code: P25130.CONSULTAR DISPONIBILIDAD

  • Nr. reclosures: Adjustable: 0,1,2,4,6,8
  • Time betwen reclosures: 0.5,1,2,3,4,5 min

INFORMATION

Description

Self-reclosing electronic relay of motorized circuit breakers. The relays of the RRM series can be used to control, send remote signals and for the remote control of the associated motorized circuit breaker (MT series).

The RRM relay has the following functions:

  • Motorized circuit breaker control:
  • Automatic reclosing
  • Remote connection/disconnection (non-reclosing)

Signalling:

  • Local, with LED
  • Remote signalling with relay of the reclosing lock (in RRM-P)
  • RS-485 Communications (in RRM-C)
Remote control of the automatic switch

The complete reclosing group is composed of the following elements:

  • Motorized circuit breaker of the MT series (2 or 4 poles)
  • Control relay RRM.

Applications

The RRM relays can be used in all applications that require a self-reclosing motorized circuit breaker after a trigger or with the use of remote control systems. It has been specially designed to work with the circuit breakers of the MT series.

SPECIFICATIONS

AC power supply
Nominal voltage
230 V ~
Frequency
50/60 Hz
DC power supply
Nominal voltage
12 Vdc ( ±20 %) without polarity
Digital relay outputs
Nominal voltage
250 V ~ (motor control contact)
Insulation voltage
250 V ~ (motor control contact)
Nominal current
1 A ~ (motor control contact)
Other digital relay outputs
Mechanical life
3x106 (signalling contact)
Nominal voltage
24 V dc (signalling contact)
Nominal current
1 Adc (signalling contact)
Environmental characteristics
Working temperature
-10 … +50 ºC
Protection class
IP 20 (terminals), IP 41 (rear panel)
Mechanical characteristics
Fastening
DIN rail
Weight (kg)
0,09
Size (mm) width x height x depth
17.5 x 85 x 68 (mm)
Protection
Circuit breaker type
Motorised circuit breaker (MT series)
LED indication
Voltage presence and circuit breaker trip number Trip indication via external order End-of-reclosing sequence interlocking During the reclosing process
Thermal-magnetic protection
Breaking capacity
Defined by the circuit breaker used
Nominal current In (A)
Definido por el magnetotérmico utilizado
Standards
Standards
IEC 60947-2

DIMENSIONS

CONNECTIONS