Station with 8 current relays, display and RS-485 communications

CDR-8

CDR-8

Code: P32111.CONSULTAR DISPONIBILIDAD

  • 8 current relays station, display, RS-485 communications. Measurement range 0,03 to 63 A

INFORMATION

Description

The CDR-8 unit measures, calculates and displays the current of 8 independent channels. Each channel can be configured as an earth leakage or current relay. It measures the true root mean square, taking decisions about the operations being carried out. It can work as a maximum or minimum current relay or as an earth leakage relay. The CDR-8 can show the earth leakage current and status of the operations relay of each of the 8 channels on an LCD display.

The device comprises :

  • 8 input channels: Measurement using WG and/or WGP series transformer.
  • 8 operation relay outputs (1 per channel)
  • 1 alarm relay
  • Operation logging recording
  • RS-485 PC communication
  • Auto-reset programming option (on RS-485 differential channels)
  • RS-485 PC communication The "PowerStudio" PC software enables you to display, record, create graphs and logs, etc.

Applications

This unit can be used to measure and control the current of up to 8 lines, with a set of reduced dimensions.

SPECIFICATIONS

AC power supply
Consumption
4 VA
Frequency
50 / 60 Hz
Nominal voltage
230 V~ (-15 … +15%)
Mechanical characteristics
Size (mm) width x height x depth
140 x 110 x 70 (mm)
Envelope
Self-extinguishing plastic
Cable gauge at power supply terminals
≥ 1mm2
Fastening
DIN 46277 (EN 50022)
Weight (kg)
0,7
Environmental characteristics
Protection class
IP 20 (terminals), IP 41 (front)
Relative humidity (without condensation)
5 … 95 %
Working temperature
-10 … +50 ºC
Communications
Fieldbus (ModBus)
RS-485
Stop bits (ModBus)
1 / 2
Parity
without, even, odd
Protocol
Modbus
Speed
4800-9600-19200 Bd
Peripheral number
1 … 255
Standards
Electrical safety, Maximum height (m)
2000
Electrical safety, Installation category
CAT III 300 V (IEC 61010)
Standards
IEC 1008, IEC 1010, IEC 60255-5, UNE 20801-2, UNE 20801-3, UNE 20801-4, UNE-EN 60730-1, IEC 61010
Electrical safety
Insulation
Class II
User interface
LED
5
Keyboard
4 push button
Digital relay outputs
Type
NO/NC
Measurement accuracy
Phase current measurement
5 % (Measurement condition: temperature +5 … +45 ºC)
Differential protection
Delay time (t∆)
0,10 - 0,4 - 0,8 - 1 - 3 - 5 - 10 s INS/SEL
Protection
Measure
True root mean square (TRMS)
Reclosure type
Reclosure number
Programmable 0 … 10