Current detector relay (AC), DIN rail

WI/005-30

WI/005-30, Current relay

Code: P32011.

  • Trip time (adjustable): 0,5 … 30 s
  • Margin of setting (adjustable): 0,5 … 5 A

INFORMATION

Description

The WI current detectors are electronic devices with an output relay that is connected or disconnected, in accordance with the level of current detected in the circuit.

  • The trip level is adjusted with the potentiometer on the front of the unit.
  • The reset process is automatic with currents under 10% of the trip level (Hysteresis).
  • Delay: the connection and disconnection times of the output relay can be adjusted separately.
  • Measurement of the current, depending on the type:
    • With built-in current transformer (net diameter ∅ 25 mm)
    • Separate transformer, input.../5 A ~

Applications

WI's can be used in any application that needs to control the load:

  • Power supply units for grinders or aggregate grinding units.
  • Loads in extrusion machines
  • Pump control
  • Load on motors, etc.

SPECIFICATIONS

AC power supply
Nominal voltage
220-240 V~ (-15%, +10%)
Frequency
50 Hz
Voltage measurement circuit
Insulation voltage
2,5 kV
Digital relay outputs
Insulation voltage
250 V ~
Thermal current (Ith)
5 A
DC11 Ie/Ue
1,6 A / 30 Vdc
AC11 Ie/Ue
0,8 A / 240 V~
Electrical life
1 x 105
Mechanical life
2 x 106
Differential protection
Sensitivity (I∆n), A
0,5 … 5
Delay time (t∆)
0,5 … 30 s
Mechanical characteristics
Weight (kg)
0,19
Size (mm) width x height x depth
70 x 87 x 75 (mm)

DIMENSIONS

CONNECTIONS

VIDEOS

DOWNLOADS

User's manual
Dimensions
Diagram connection
Datasheet

ACCESORIES

TAMBIÉN TE PUEDE INTERESAR