Measuring and testing equipments for substations

GETEST 5...50A

GETEST 5...50A, Indirect earth contact simulator 5 ... 50 A, Smartphone included,

Code: P6012300A0000

    INFORMATION

    Description

    The MPC-5/50 GETEST is used to measure voltages between points on the ground (step potential) or between ground and conductive parts (contact potential) when there are leakage currents through the ground connection. These readings are required in Spain in transformer and distribution centres, as per MIE-RAT-13, BOE RD 337/2014, of 9 May. To conduct the test, the current source is connected between points far away from a ground line, and the voltage between two weights one-meter apart is measured (step potential), or between the ground and accessible conductive parts. The current source is adjusted to the desired value by means of a smartphone or tablet, allowing the measured data to be viewed and stored. 

    • Step and contact meter, based on injecting current during one network cycle (20 ms) (maximum safety during use).
    • Earth resistance measurement.
    • Provides up to 50 A with a 12 Ω load. Maximum output voltage of 700 VAC.
    • Maximum power equivalent to 30 kV·A, with a weight of just 45 kg.
    • Remote control and display of the data measured on a smartphone or tablet, connected wirelessly to the device.
    • Data storage on the smartphone or tablet itself, easily transferred to a PC.

    SPECIFICATIONS

    AC power supply
    Nominal voltage
    230 V ~ ± 20% (L1-N)
    Frequency
    50 … 60 Hz
    Input intensity
    15 A ~
    Installation category
    CAT II 300 V
    Electrical characteristics
    Resistance measurement
    0 … 120 Ω
    Voltage measurement circuit
    Voltage measuring range
    0.8, 30, 70, 105, 280 and 700 V ~ (Self-adjusting)
    Input impedance
    1 KΩ, 2 KΩ, 10 MΩ
    Maximum value
    700 V~
    Installation category
    CAT II 300 V
    Current measurement circuit
    Maximum current
    100 A ~
    Impedance
    < 0.1 Ω
    Resolution
    Scale: 10 A(0.01 A~) Scale: 100 A (0.1 A ~)
    Measurement accuracy
    Accuracy
    2.5 % reading + 2 digits
    Environmental characteristics
    Working temperature
    0 … +40 ºC
    Storage temperature
    -10 … +50 ºC
    Relative humidity (without condensation)
    5 … 95 %
    Mechanical characteristics
    Envelope
    Steel / Aluminium
    Weight (kg)
    90
    Size (mm) width x height x depth
    285 x 340 x 285 (mm)
    Standards
    Standards
    UNE-EN 61010-1, UNE-EN 610110-2-03, UNE-EN 61326-1
    Electrical safety, Maximum height (m)
    2000