Power factor regulators for static switching

computer SMART III Fast 6

computer SMART III Fast 6, Power factor regulator

Code: R13951.

  • Alarm relay: Yes
  • Communications: RS-485
  • Measurement Range (V): 100...520
  • IΔn (A): yes
  • Power supply (Vac): 100...520 Vac
  • Nr steps: 6
  • Input current: .../5A | .../1A
  • Switching unit: EMF / EMB

INFORMATION

Description

Measurement with three current transformers guarantees an analogue reading of the company meter. The Computer SMART III Fast reactive energy regulator is the only regulator on the market that offers the possibility of using 3 measurement transformers in addition to the conventional method of measuring with a single current transformer, as well as providing the functions of an integral power analyzer and controlling residual leakage currents.
Computer SMART III Fast is a regulator that ensures excellent preventive maintenance by means of programming its alarms and the options for testing the capacitor status, offering maximum supervision and safety of your compensation unit.

Applications

Computer Smart III fast it’s the ideal solution to compensate installations with a variation of quick load, between 40 ms and 4 seconds, and/or large unbalances between phases, such as welding units, cranes, lifts and lifting units, smelters, hospitals, automotive industry or any other sector or unit that requires an efficient compensation of the power factor.
The connection of 1 or 3 transformers makes computer SMART III Fast the perfect regulator in any installation, allowing the following:

  • Changing from 1 to 3 transformers in the following cases:
    • Single-phase fast changing equipment
    • Example: Single-phase welding
    • Replacing the regulator of any capacitor bank
  • Perfect for installations with up to 4 objective cos φ, since it can adapt to any compensation need (different time periods).

SPECIFICATIONS

AC power supply
Installation category
CAT III 300 V
Consumption
8 … 14 VA
Frequency
50 … 60 Hz
Nominal voltage
100 ... 520 V ~
Mechanical characteristics
Size (mm) width x height x depth
144 x 144 x 71 (mm)
Envelope
Plastic V0 self-extinguishing
Fastening
Panel
Weight (kg)
0,44
Environmental characteristics
Protection class
IP 51 (Front), IP 31 (unmounted)
Relative humidity (without condensation)
5 … 95%
Storage temperature
-20 … +70 ºC
Working temperature
-10 … +55 ºC
Current measurement circuit
Installation category
CAT III 300 V
Nominal current (In)
.../5A ó .../1A
Phase current measuring range
1 … 120 % In
Minimum current measurement
50 mA
Voltage measurement circuit
Installation category
CAT III 300 V
Sampling frequency
45 … 65 Hz
Input impedance
660 kΩ
Frequency measuring range
45 … 65 Hz
Voltage measuring range
20...300 V Ph-N , 35...520 V Ph-Ph
Nominal voltage
230 V Ph-N, 400 V Ph-Ph
Minimum measurement voltage (Vstart)
20 V F-N, 35 V F-F
Communications
Fieldbus (ModBus)
RS-485
Parity
without, even, odd
Protocol
Modbus RTU
Type
CPC-NET / RS-485
Speed
RS-485: 9600-19200 / CPC-NET: 9600-19200-38400
Stop bits
1-2
Standards
Electrical safety, Maximum height (m)
2000
Standards
IEC 61010, IEC 61000, IEC 61000-6-2, IEC 61000-6-4, Medidas conforme a : IEC 61557-12
User interface
LED
4 LED
Keyboard
Capacitive, 5 keys
Display type
LCD Custom COG
Digital inputs
Input/output insulation
Optoisolated
Quantity
2
Type
Potential-free contact
Leakage current measurement (ID)
Secondary nominal current
0,003 A
Minimum current measurement (Istart)
10 mA
Measurement range
0,01 … 1,5 A
Other digital transistor outputs
Quantity
2
Type
NPN
Maximum current
50 mA
Maximum voltage
24 Vcc
Digital relay outputs
Quantity
2 (ventilador, alarma)
Maximum current
1A
Maximum open contact voltage
1 kV
Electrical life
30 x 103 ciclos
Mechanical life
5 x 106 Cycles
Maximum switching capacity
2500 VA
Digital transistor outputs
Quantity
6
Type
Opto MOSFET
Maximum current
150 mA
Maximum voltage
24 Vcc
Measurement accuracy
Phase current measurement
0.5% ± 1 digit
Reactive energy measurement (kvarh)
Class 1
Reactive power measurement (kvar)
1% ± 2 digit
Active energy measurement (kWh)
Class 1
Active power measurement (kW)
0.5% ± 2 digits
Phase voltage measurement
0.5% ± 1 digit

DIMENSIÓN

VÍDEOS

SMART III. Integral Power Factor relay: Compensation, Analysis and Protection

CIRCUTOR Capacitor bank start up with Computer SMART III regulator
Basic programming of Computer SMART III / SMART III Fast regulator
Advanced programming of Computer SMART III / SMART III Fast regulator

DESCARGAS

User's manual
Technical guide
3D
Dimensions
Diagram connection
Configuration guide
Datasheet
Catalogue
Leaflet
Product video
Video Installation
Software & Firmware

ACCESORIOS

TAMBIÉN TE PUEDE INTERESAR