Power factor relay 1 step. DIN rail

DIR2

DIR2, Reactive relay

Code: R11211.

  • Alarm relay: No
  • Power supply (Vac): 400 Vac
  • Nr steps: 1
  • Input current: .../250 mA
  • Switching unit: Contactor

INFORMATION

Description

The DIR2 Power Factor Relay is capable of acting on a circuit in accordance with the reactive inductive or capacitive current transmitted through it. The DIR2 relay measures reactive current in mA of the secondary of a .../250 mA current transformer MC1 or MC3 type. The front of the relay has a control panel that is used to adjust the reactive current where the relay will act. It has a LED that indicates the status of the relay.

Applications

The DIR2 relay is easy to install and program, making it the best solution in the following applications:

  • Individual compensation of small, medium or large power loads.
  • Partial compensation in installations with automatic equipment available.
  • Partial or total regulator in low-power installations.Instantaneous and total disconnection of capacitor banks when there is a high capacitive current in the network.
  • Control of reactive currents- capacitive and inductive - triggering an alarm signal when a high current is detected.

SPECIFICATIONS

AC power supply
Nominal voltage
400 V ~ ±10%
Frequency
50-60 Hz
Consumption
< 3 VA
Current measurement circuit
Nominal current (In)
0,25 A ~
Allowable overload
1,2 In
Consumption
< 0,05 VA
Permanent overload
1,2 In
Idle current tripping
C/K trip adjustment range
0,15 … 2
Connection delay Tc
5 s
Disconnection delay Tr
2 s
Digital relay outputs
Thermal current (Ith)
10 A
DC11 Ie/Ue
0,3 A / 110 V dc
AC11 Ie/Ue
10 A / 250 V ~
Electrical life
10x10 4 maniobras
Mechanical life
10x106 operations
Environmental characteristics
Working temperature
-10 … +50 ºC
Relative humidity (without condensation)
95%
Protection class
IP 40
Standards
Standards
EN 61010, EN 61000-3-2, EN 61000-3-3, EN 50081-2, EN 50082-1, EN 50082-2, EN 61000-4-2, EN 61000-4-4, EN 61000-4-8, EN 61000-4-5, EN 61000-4-11, UL 94
Certifications
UL
Electrical safety, Maximum height (m)
2000
Electrical safety
Insulation
Double-insulated electric shock protection class II (IEC 61010-1)
Mechanical characteristics
Weight (kg)
0,1
Size (mm) width x height x depth
35 x 85 x 73 (mm)

DIMENSIONS

CONNECTIONS

VIDEOS

DOWNLOADS

User's manual
Dimensions
Datasheet