Choke reactors for MV capacitor banks

RMV-330-125-100

RMV-330-125-100, Choke reactor

Code: R80774.

  • In (A): 125

INFORMATION

Description

Choke REACTORS are required to limit the transient currents produced during the connection of capacitors. CIRCUTOR's RMV units are encapsulated in epoxy resin, which guarantees the degree of insulation required.

Applications

The connection of capacitor banks has very high associated transient currents and voltages. The IEC 60871-1 Standard defines the maximum value that can be supported by a capacitor bank as the peak connection value. This value is 100 times its nominal current. 
When this value is exceeded, RMV choke REACTORS must be installed. These REACTORS are in charge of limiting the transient current to values that can be supported by the capacitors. The inductance value is variable, depending on the installation's conditions and, basically, on the following parameters:

  • Short-circuit power of the installation
  • Existence of more capacitor banks
  • Interrupting power of automatic switches. The peak current value of the residual connection must also be lower than the interrupting power of the switch unit after the reactor has been installed.

SPECIFICATIONS

Current measurement circuit
Nominal current (In)
43 In / 1 s
Mechanical characteristics
Envelope
colour RAL 8016
Fastening
M12 / M16, depending on the type
Material
Encapsulated in resin, Air core.
Weight (kg)
22
Size (mm) width x height x depth
470 x 355 x 110 (mm)
Standards
Standards
IEC 60289

DIMENSIONS

CONNECTIONS

VIDEOS

DOWNLOADS

3D
Datasheet
CE-certified
Catalogue
Leaflet