Harmonic filters

AFQm-3WF-075M-480

AFQm-3WF-075M-480, Active multifunctionfilter, 3 wires

Code: R7MMAF.

  • System: 3 wires, 230...480 V
  • Phase current (A): 75
  • Peak current (A): 150
  • Mounting: Wall-mounted

INFORMATION

Description

The wall-mounted AFQm multilevel active filters are the most complete solution for solving power quality problems in three-phase industrial, commercial or service installations caused by the presence of harmonics and the consumption of reactive power. These following characteristics and functions have been implemented:

  • Filtering capacity of 30 A, 75 A and 100 A
  • Small wall-mounted cabinet easy to install thanks to its small dimensions
  • Range for installations with 3 wires (3W model) or 4 wires (4W model)
  • Multi-range voltage and dual frequency (50/60 Hz)
  • Reduction of harmonic currents up to the fiftieth harmonic (2,500 Hz)
  • Selection of harmonic frequencies to be filtered for maximum filter effectiveness
  • Power factor correction both inductive and capacitive
  • Phase current balancing, improvement of consumption in neutral (4W model)
If higher filtering capabilities are required, up to 100 filters can be connected in parallel (the filters must all be of the same 3 or 4-wire model).

Applications

They are an ideal solution for installations with a large amount of single-phase and three-phase loads generating harmonics, such as computers, UPS units, lights, lifting equipment, air-conditioning systems with variable speed drives, etc.
They can also be used in installations that require a good power quality for the purpose of increasing production efficiency and improve supply continuity in the system.

SPECIFICATIONS

AC power supply
Nominal voltage
208 … 480 V~ F-F (± 10 %)
Frequency
50 / 60 Hz (± 5 %)
Consumption
1550 W
Electrical characteristics
Maximum phase current
75 A (RMS)
Current crest factor
2:1
Earthing system
TN, TT
Current measurement circuit
Transformation ratio
5 … 5000 / 5A
Measurement accuracy
Voltage harmonics (THD)
25 % (max)
Power supply output
Power
45812 VA
Serial communication
Technology / Type
RS-485
Protocol
Modbus/RTU
Communication Network
Technology / Type
Ethernet
Protocol
TCP/IP, Modbus TCP
User interface
Display type
TFT color, 3.5" touchscreen
Environmental characteristics
Working temperature
-10 ... +45 ºC
Storage temperature
-20 ... +50 ºC
Relative humidity (without condensation)
0 ... 95 %
Protection class
IP 20
Mechanical characteristics
Envelope
Galvanized steel 1,5 mm
Connection type
Network / Ground: M6 terminals, Current: 6-pole connector, RS-485: 3-pole connector, Ethernet: RJ-45
Weight (kg)
56
Size (mm) width x height x depth
439 x 745 x 288 (mm)
Features / performance
Filtering / Response time
2º … 50º harmonic (selectable) / < 100 µs
Phase compensation
Selectable
Reactive power compensation (Kvar)
selectable
Priority scheduling
selectable
Parallel assembly/installation
Up to 100 units, with different gauges. Transformer connection only to the Master unit
Standards
Standards
IEC 62477-1:2012, IEC 55011:2011, IEC 61000-6-2, IEC 61000-6-4:2007,IEC 61439-1:2011
Electrical safety, Maximum height (m)
3000 (2000 m without performance degradation)

DIMENSIONS

CONNECTIONS

VIDEOS

DOWNLOADS

User's manual
Dimensions
Diagram connection
Datasheet
Presentation
CE-certified
Video Installation
Other Certificates

Application Notes
Active Filter installation guidelines
Commissioning of active filters
Replacement guide : Replacement of a Rack type AFQevo with an AFQm
Expansion guide : Installation of a Rack type AFQm in an AFQevo cabinet / Installation of a Rack type AFQm in an AFQm cabinet
Installation guide for a cabinet type AFQm