Harmonic filters for power converters

LC L36-40A-480

LC L36-40A-480, Filter

Code: R732100070000

  • Load current (A): 40
  • Frequency (Hz): 60
  • Q (kvar): 11,38
  • cabinet: OPTIM5

INFORMATION

Description

LCL filters have been specially designed to eliminate the harmonics from the current absorbed by 6-pulse power converters, such as frequency variators for motors, UPS, etc. These are essentially passive filters based on a series-parallel combination of inductances and capacitors, adapted to filter the input of power converters.

Applications

  • Reduction of the current wave's distortion towards the network and the rest of the installation.
  • Compliance with the IEC 61000-3-4, IEC 61000-3-12, IEC 61800-3 and IEEE-519.
  • Energy savings with the reduction of the root mean square current (RMS), thus reducing the kV·A demand.
  • Increase of the working life of units above this location with the corresponding reduction of thermal losses generated.
  • Limits current transients, preventing damages caused to the converter and overvoltage trips that affect production processes.

SPECIFICATIONS

AC power supply
Nominal voltage
400 Vca /480 Vca F-F (otras tensiones, bajo demanda)
Frequency
60 Hz
Electrical characteristics
Residual current THD
Approx. 8%
Nominal current voltage drop
< 2 %
Filtered current If (RMS)
16 A
LC load current (RMS)
40 A
Current measurement circuit
Allowable overload
1,5 Ic (≤ 1 min.) + Ic (≤ 5 min.) (at maximum operating temperature)
Environmental characteristics
Operating temperature
+ 35 ºC
Relative humidity (without condensation)
80%
Protection class
IP 20
Mechanical characteristics
Envelope
Treated and painted steel. Frame RAL 1013 / Doors RAL 3005
Fastening
On the ground
Size (mm) width x height x depth
460 x 930 x 230 (mm)
Standards
Standards
UNE-EN 60439 , UNE-EN60831 , IEC 61000-6-3 , IEC 61000-6-4, Class A

DIMENSIONS

CONNECTIONS

VIDEOS

DOWNLOADS

User's manual
Diagram connection
Datasheet
Catalogue
Leaflet

ACCESORIES