Accesorios para AR5L

SPECIFICATIONS

AC power supply
Nominal voltage
100…240 Vc.a./12 Vc.c. (a través de alimentador externo)
Frequency
50…60 Hz
Consumption
15 VA
Voltage measurement circuit
Frequency measuring range
45…65 Hz
Sampling frequency
45…65 Hz
Current measurement circuit
Phase current measuring range
According to clamp
Transformation ratio
Programmable
Measurement units
Automatic scale change
Measurement accuracy
Phase voltage measurement
0,5% ±2 digit
Phase current measurement
0,5% ±2 digit
Active power measurement (kW)
1% ±2 digit
Reactive power measurement (kvar)
1% ±2 digit
User interface
Display type
LCD
Resolution of the display
160 x 160 pixels (Backlight)
Environmental characteristics
Working temperature
0 … +40 °C
Relative humidity (without condensation)
80% para temperaturas inferiores a 31 ºC, disminuyendo linealmente hasta 50% a 40 ºC
Standards
Standards
IEC 60664, IEC 61010, IEC 61036, VDE 0110 , UL 94, IEC 61000-3-2(1995), IEC 61000-3-3(1995), IEC 50081-2(1993), EN 55011 (1994): Conducted (EN 55022-Class B), Radiated (EN 55022-Class A), EN 50082-2 (1995), IEC 61000-4-8 (1995), IEC 61000-4-2 (1995), UNE-ENV 50141
Certifications
UL, VDE
Electrical safety, Installation category
CAT III 600V, IEC 61010
Electrical safety, Maximum height (m)
≤ 2000
Mechanical characteristics
Weight (kg)
0,126
Size (mm) width x height x depth
40 x 61.65 x 9 (mm)

DIMENSIONS

CONNECTIONS

VIDEOS

DOWNLOADS

ACCESORIES