Motorised circuit-breaker

MT-TS- 250A- 3P

MT-TS-250A-3P, Motorised MCB, 3 poles

Code: P20H64.

  • Poles: 3
  • In (A): 250 A

INFORMATION

Description

MT-TS series automatic switch with remote control for currents from 80 to 630A, with both 3 and 4 poles.
Provides short-circuit and overload protection, and is also used as a circuit breaker.

The switch can be reconnected in two ways, depending on how the operation mode is set in the motor group:

  • “MANU”: done manually on the switch itself by turning it to OFF and then ON.
  • “AUTO”: done by means of an electrical impulse that follows the OFF-ON sequence.

Applications

The MT-TS series are motorized automatic switches that can be operated remotely and are valid for any application that requires remote connection/disconnection. They are an essential component for providing overload protection with reclosing.

SPECIFICATIONS

DC power supply
Nominal voltage
500 V
Electrical characteristics
Insulation voltage, circuit
1000 V
Mechanical life
25000 cycles
Electrical lifetime
10000 cycles 415 V In
Environmental characteristics
Working temperature
-20 … +70 ºC
Storage temperature
-40 … +70 ºC
Protection class
IP20, IEC 60529
Protection
Circuit breaker type
Class A
Thermal-magnetic protection
Nominal current In (A)
250
Rated short-circuit marking capacity (IEC 60947-2) (Icm)
220 kA at 220/240 Vac 50/60 Hz. 105 kA at 380/415 Vac 50/60 Hz. 105 kA at 440/460 Vac 50/60 Hz. 88 kA at 480/500 Vac 50/60 Hz. 46 kA at 525 Vac 50/60 Hz. 17 kA at 660/690 Vac 50/60 Hz.
Thermal adjustment (Ir)
Adjustable, 3 settings: 0.8 / 0.9 / 1 x In
Magnetic adjustment (Ii)
Fixed 10 x In
Ultimate short-circuit breaking capacity (Icu) / service short-circuit breaking capacity (Ics), in DC (IEC 60947-2)
50 kA at 250 Vdc, reference 50 kA at 500 Vdc (2poles in series), reference
AC ultimate short-circuit breaking capacity (Icu) (IEC 60947-2)
100 kA at 220/240 Vac 50/60 Hz. 50 kA at 380/415 Vac 50/60 Hz. 50 kA at 440/460 Vac 50/60 Hz. 42 kA at 480/500 Vac 50/60 Hz. 22 kA at 525 Vac 50/60 Hz.
Circuit breaker / RCCB
Rated nominal voltage (Un)
690 V ~
Assigned frequency (Hz)
50 / 60 Hz
Standards
Standards
IEC 60947-2, IEC 60664-1
Electrical safety, Contamination level/class
Pollution resistance 3
Mechanical characteristics
Weight (kg)
3,6
Size (mm) width x height x depth
105 x 160 x 195 (mm)

DIMENSIONS

CONNECTIONS

VIDEOS

DOWNLOADS

3D
Datasheet

ACCESORIES