Data: non-volatile memory, Setup and events: serial-flash
Voltage measurement circuit
Nominal voltage
3x63,5/110 V
Consumption
< 2 W; 10 VA
Nominal frequency
50 / 60 Hz
Connection
Asymmetrical
Current measurement circuit
Maximum current
10 A
Minimum current measurement
< 0,5 x Itr
Reference current (Iref)
…/ 5 A
Consumption
< 0,1 V·A
Measurement accuracy
Active energy measurement (kWh)
IEC 62053-22 (Class 0,5S)
EN 50470 (Class C)
Reactive energy measurement (kvarh)
IEC 62053-23 (Class 1 / 2)
Serial communication
Technology / Type
RS-485
Protocol
REE, basado en IEC 870-5-102
Communication Network
Technology / Type
Ethernet
Protocol
REE, basado en IEC 870-5-102
User interface
Display type
LCD
Resolution of the display
up to 8 digits (8 mm)
Environmental characteristics
Working temperature
-25 ... +70 ºC
Storage temperature
-40 ... +85 ºC
Relative humidity (without condensation)
95 % max.
Standards
Standards
UNE-EN 50470-1 Electricity metering equipment (a.c.) -- Part 1: General requirements, tests and test conditions - Metering equipment -class indexes B-)
UNE-EN 50470-3 Electricity metering equipment (a.c.) -- Part 3: Particular requirements - Static meters for active energy -class indexes B-)
IEC 62052-11, IEC 62053-21, IEC 62053-22 (Standards for static active energy meters for alternating current of class 0.2s, 0.5s)
UNE-EN 55022 (Conducted Emissions: Class B, Radiated Emissions: Class B)
UNE-EN 61000-4-2, UNE-EN 61000-4-3, UNE-EN 61000-4-4, UNE-EN 61000-4-5, UNE-EN 61000-4-6, UNE-EN 61000-4-8, UNE-EN 61000-4-11