Process universal transducer

CUP Out 2

CUP Out 2, Transducer

Code: M25612.CONSULTAR DISPONIBILIDAD

  • Output type: 1,2,3
  • Analog output: 0…20mA | 4…20mA
  • Measure: Configurable

INFORMATION

Description

The universal process transducers have been designed to adapt different process signals or to have a galvanic isolation between the input and output circuit.
The input and output can be configurated by the user.through internal jumpers. It is not necessary to adjust zero or span if the user decide to change the configuration.

SPECIFICATIONS

AC power supply, insulation
Pulse test (kV)
3 kV (1,2/50µs)
Test voltage (kV)
2 kV RMS 50 Hz 1min
AC power supply
Consumption
2,5 VA
Frequency
40…90 Hz
Nominal voltage
115/230/400 Vca (-15…+20 %)
DC power supply, insulation
Pulse test (kV)
3 kV (1,2/50µs)
Test voltage (kV)
2 kV RMS 50Hz 1 min
DC power supply
Consumption
2,5 VA
Nominal voltage
9-18 / 18-36 Vdc 36-72 / 90-140 Vdc
Mechanical characteristics
Size (mm) width x height x depth
40 x 72 x 110 (mm)
Weight (kg)
0,3
Environmental characteristics
Protection class
IP 20 (Terminals) IP 40 (case)
Storage temperature
-40….+70 °C
Working temperature
-10…+55 °C
Current measurement circuit
Nominal current (In)
20 mA
Phase current measurement
0…150 % In
Voltage measurement circuit
Nominal voltage
10 V
Maximum permanent measurement voltage
200 % Vn
Standards
Electrical safety, Maximum height (m)
2000
Standards
IEC 529, IEC 688, IEC 801, IEC 1010
Analogue inputs
Load impedance in current
< 500 Ω
Ripple (effective RMS value)
< 0,5 %
Load impedance in voltage
> 500 Ω
Response time
< 300 ms (0…99 % Vn)
Analogue outputs
Current mode, nominal range
0…10, 20 mAac
Displaced output
0,2…2 V / 2…10 V / 4…20 mA
Voltage mode: nominal output range
-10, -5 … 0 … 5, 10 V
Measurement accuracy
Phase current measurement
0,2 % FS

DIMENSIONS

CONNECTIONS

VIDEOS

DOWNLOADS

User's manual
Dimensions
Datasheet

ACCESORIES