Galvanic insulator transducer

CC-G

CC-G, Isolation transducer

Code: M25610.CONSULTAR DISPONIBILIDAD

  • Output type: 1
  • Analog output: 0…20mA
  • Measure: 500 µA … 10 Adc

INFORMATION

Description

The CC-G transducers, convert D.C current to D.C process indicator signal, and it can be used for galvanic separation between the input and output circuits.

The analog output is directly proportional to the input signal.

SPECIFICATIONS

AC power supply, insulation
Pulse test (kV)
4 kV (1,2/50µs)
Test voltage (kV)
3 kV RMS 50 Hz 1min
AC power supply
Consumption
2,5 VA
Frequency
40…90 Hz
Nominal voltage
24/115/230/400 Vca (-15…+20 %)
DC power supply, insulation
Pulse test (kV)
3 kV (1,2/50µs)
Test voltage (kV)
2 kV RMS 50Hz 1 min
DC power supply
Consumption
2,5 VA
Nominal voltage
9-18 / 18-36 Vdc 36-72 / 90-140 Vdc
Mechanical characteristics
Size (mm) width x height x depth
40 x 72 x 110 (mm)
Weight (kg)
0,29
Environmental characteristics
Protection class
IP 20 (Terminals) IP 40 (case)
Storage temperature
-40….+70 °C
Working temperature
-10…+55 °C
Current measurement circuit
Nominal current (In)
500 µA … 10 A
Phase current measurement
0…120 % In
Allowable overload
300 % In permanent
Maximum current
15 A
Standards
Electrical safety, Maximum height (m)
2000
Standards
IEC 529, IEC 688, IEC 801, EN 50081-2, EN 50082-2, IEC 1010
Analogue inputs
Load impedance in current
< 500 Ω
Ripple (effective RMS value)
< 0,5 %
Load impedance in voltage
> 500 Ω
Response time
< 100 ms (0…99 % Vn)
Analogue outputs
Current mode, nominal range
0…10, 20 mAac
Displaced output
0,2…2 V / 2…10 V / 4…20 mA
Voltage mode: nominal output range
0…5, 10 Vac
Measurement accuracy
Phase current measurement
0,2 % FS