Power Factor transducer

CPF-M Out1,3

CPF-M Sal.1,3

Code: M25311.CONSULTAR DISPONIBILIDAD

  • Transducer FP
  • Output type: 1
  • 3
  • Analog output: 0…20mA
  • System: Single-phase

INFORMATION

Description

The CPF transducers measure power factor single phase.
The analog output is directly proportional to the measurement signal, 0...20 mA or 4...20 mA. The analog output can be bidirectional.

SPECIFICATIONS

AC power supply
Nominal voltage
24/115/230/400 Vca (-15…+20 %)
Frequency
40…90 Hz
Consumption
2,5 VA
AC power supply, insulation
Test voltage (kV)
3 kV RMS 50 Hz 1min
Pulse test (kV)
4 kV (1,2/50µs)
DC power supply
Nominal voltage
9-18 / 18-36 Vdc 36-72 / 90-140 Vdc
Consumption
2,5 VA
DC power supply, insulation
Test voltage (kV)
2 kV RMS 50Hz 1 min
Pulse test (kV)
3 kV (1,2/50µs)
Voltage measurement circuit
Nominal voltage
500 Vca
Voltage measuring range
10…150 % Vn
Frequency measuring range
45…65 Hz
Maximum permanent measurement voltage
1000 V
Consumption
0,2 VA
Current measurement circuit
Nominal current (In)
5A
Phase current measurement
0,5…6 In
Allowable overload
300 % In permanent
Measurement accuracy
Phase current measurement
0,5 % FS
Analogue outputs
Current mode, nominal range
0…20 mAac / 4…20 mAac
Analogue inputs
Load impedance in current
< 500 Ω
Response time
< 500 ms (0…99 % Vn)
Ripple (effective RMS value)
< 0,5 %
Environmental characteristics
Working temperature
-10…+55 °C
Storage temperature
-40….+70 °C
Protection class
IP 20 (Terminals) IP 40 (case)
Standards
Standards
IEC 529, IEC 688, IEC 801, EN 50081-2, EN 50082-2, IEC 1010
Electrical safety, Maximum height (m)
2000
Mechanical characteristics
Weight (kg)
0,2
Size (mm) width x height x depth
95 x 72 x 110 (mm)