Cosϕ transducer

CCOS-TEN Sal1,3

CCOS-TEN Sal1,3

Code: M25361.CONSULTAR DISPONIBILIDAD

  • Transducer FP
  • Output type: 1
  • 3
  • Analog output: 0…20mA
  • System: Balanced three-phase (4 wires)

INFORMATION

Description

The CCOS transducers measure cosφ  single-phase system.
The analog output is directly proportional to the measurement signal, 0...20 mA or 4...20 mA. The analog output can be bidirectional.

SPECIFICATIONS

AC power supply, insulation
Pulse test (kV)
4 kV (1,2/50µs)
Test voltage (kV)
3 kV RMS 50 Hz 1min
AC power supply
Consumption
2,5 VA
Frequency
40…90 Hz
Nominal voltage
24/115/230/400 Vca (-15…+20 %)
DC power supply, insulation
Pulse test (kV)
3 kV (1,2/50µs)
Test voltage (kV)
2 kV RMS 50Hz 1 min
DC power supply
Consumption
2,5 VA
Nominal voltage
9-18 / 18-36 Vdc 36-72 / 90-140 Vdc
Mechanical characteristics
Size (mm) width x height x depth
95 x 72 x 110 (mm)
Weight (kg)
0,31
Environmental characteristics
Protection class
IP 20 (Terminals) IP 40 (case)
Storage temperature
-40….+70 °C
Working temperature
-10…+55 °C
Current measurement circuit
Nominal current (In)
5A
Phase current measurement
0…150 % In
Allowable overload
300 % In permanent
Voltage measurement circuit
Consumption
0,2 VA
Frequency measuring range
45…65 Hz
Voltage measuring range
0…150 % Vn
Nominal voltage
500 Vca
Maximum permanent measurement voltage
1000 V
Standards
Electrical safety, Maximum height (m)
2000
Standards
IEC 529, IEC 688, IEC 801, EN 50081-2, EN 50082-2, IEC 1010
Analogue inputs
Load impedance in current
< 500 Ω
Ripple (effective RMS value)
< 0,5 %
Response time
< 500 ms (0…99 % Vn)
Analogue outputs
Current mode, nominal range
0…20 mAac / 4…20 mAac
Measurement accuracy
Phase current measurement
0,5 % FS

DIMENSIÓN

VÍDEOS

DESCARGAS

User's manual
Dimensions
Datasheet

ACCESORIOS