Narrow section AC frecuency transducer

CFE

CFE, Transducer Hz

Code: M25511.

  • Output type: 2
  • Analog output: 4…20mA
  • System: Network voltage: 50 … 600 Vac
  • Measure: 45 ...... 55 Hz

INFORMATION

Description

The CFE and CFE-AP transducers, convert input frequency to D.C process indicator signal.

The analog output is directly proportional to the input frequency.

SPECIFICATIONS

AC power supply, insulation
Pulse test (kV)
4 kV (1,2/50µs)
Test voltage (kV)
3 kV RMS 50 Hz 1min
AC power supply
Consumption
2,5 VA
Frequency
40…90 Hz
Nominal voltage
115/230 Vca (-10…+10 %)
DC power supply, insulation
Pulse test (kV)
3 kV (1,2/50µs)
Test voltage (kV)
2 kV RMS 50Hz 1 min
DC power supply
Consumption
2,5 VA
Nominal voltage
9-18 / 18-36 Vdc 36-72 / 90-140 Vdc
Mechanical characteristics
Size (mm) width x height x depth
20 x 70 x 110 (mm)
Weight (kg)
0,062
Environmental characteristics
Protection class
IP 20 (Terminals) IP 40 (case)
Storage temperature
-40….+70 °C
Working temperature
-10…+60 °C
Voltage measurement circuit
Consumption
0,2 VA
Voltage measuring range
50…660 V
Maximum permanent measurement voltage
1000 V
Standards
Electrical safety, Maximum height (m)
2000
Standards
IEC 529, IEC 688, IEC 801, EN 50081-1, EN 50082-1, IEC 1010
Analogue inputs
Load impedance in current
< 500 Ω
Ripple (effective RMS value)
< 1 %
Load impedance in voltage
> 500 Ω
Response time
< 300 ms (0…99 % Vn)
Analogue outputs
Displaced output
0,2…2 V / 2…10 V / 4…20 mA
Measurement accuracy
Phase current measurement
0,5 % FS

DIMENSIÓN

VÍDEOS

DESCARGAS

Dimensions
Diagram connection
Datasheet