Step and contact voltage meter

GETEST 5...50A

GETEST 5...50A, Indirect earth contact simulator 5 ... 50 A, Smartphone included,

Code: P6012300A0000

    INFORMATION

    Description

    The MPC-5/50 GETEST is used to measure voltages between points on the ground (step potential) or between ground and conductive parts (contact potential) when there are leakage currents through the ground connection. These readings are required in Spain in transformer and distribution centres, as per MIE-RAT-13, BOE RD 337/2014, of 9 May. To conduct the test, the current source is connected between points far away from a ground line, and the voltage between two weights one-meter apart is measured (step potential), or between the ground and accessible conductive parts. The current source is adjusted to the desired value by means of a smartphone or tablet, allowing the measured data to be viewed and stored. 

    • Step and contact meter, based on injecting current during one network cycle (20 ms) (maximum safety during use).
    • Earth resistance measurement.
    • Provides up to 50 A with a 12 Ω load. Maximum output voltage of 700 VAC.
    • Maximum power equivalent to 30 kV·A, with a weight of just 45 kg.
    • Remote control and display of the data measured on a smartphone or tablet, connected wirelessly to the device.
    • Data storage on the smartphone or tablet itself, easily transferred to a PC.

    SPECIFICATIONS

    AC power supply
    Installation category
    CAT II 300 V
    Input intensity
    15 A ~
    Frequency
    50 … 60 Hz
    Nominal voltage
    230 V ~ ± 20% (L1-N)
    Electrical characteristics
    Resistance measurement
    0 … 120 Ω
    Mechanical characteristics
    Size (mm) width x height x depth
    285 x 340 x 285 (mm)
    Envelope
    Steel / Aluminium
    Cable gauge at power supply terminals
    IEC 60320 C20 16A
    Cable gauge at current terminals
    4 mm safety banana CAT IV 600 V 32 A
    Cable gauge at voltage terminals
    4 mm safety banana CAT IV 600 V 32 A
    Weight (kg)
    90
    Environmental characteristics
    Relative humidity (without condensation)
    5 … 95 %
    Storage temperature
    -10 … +50 ºC
    Working temperature
    0 … +40 ºC
    Current measurement circuit
    Impedance
    < 0.1 Ω
    Maximum current
    100 A ~
    Resolution
    Scale: 10 A(0.01 A~) Scale: 100 A (0.1 A ~)
    Voltage measurement circuit
    Installation category
    CAT II 300 V
    Input impedance
    1 KΩ, 2 KΩ, 10 MΩ
    Voltage measuring range
    0.8, 30, 70, 105, 280 and 700 V ~ (Self-adjusting)
    Maximum value
    700 V~
    Standards
    Electrical safety, Maximum height (m)
    2000
    Standards
    UNE-EN 61010-1, UNE-EN 610110-2-03, UNE-EN 61326-1
    Measurement accuracy
    Accuracy
    2.5 % reading + 2 digits

    DIMENSIONS

    CONNECTIONS

    VIDEOS

    DOWNLOADS

    User's manual
    Dimensions
    Datasheet
    Catalogue
    CE-certified
    Software & Firmware

    ACCESORIES

    TAMBIÉN TE PUEDE INTERESAR