Fixed power analyzer

kit CVM-D441+4xSCV1

kit CVM-D441+4xSCV1, Multi-channel network analyser with memory, DIN rail

Code: M55138.

  • Protocol: Modbus/TCP |Modbus/RTU
  • Memory: Yes
  • Clamp: 3 x SVC
  • Communications: Wi-Fi | Ethernet | RS-487
  • Transistor output: 4
  • Harmonics: 15
  • Input current: .../333 mV
  • Mounting: DIN rail
  • Nª Input channels: 1...4(III) | 1...12(II)

INFORMATION

Description

The CVM-D400 series are multi-channel power analysers designed for reading multiple loads or circuits (Branch Circuit Monitoring). These devices can manage up to 12 single-phase or 4 three-phase lines or loads, or any combination of them in a single device. They also allow each type of consumption to be labelled, grouping together the total consumption of all the loads destined for the same purpose without the need for any type of programming. The results are automatically displayed on screen or via communications. The devices are configured via an integrated web interface, accessible via Wi-Fi or Ethernet, or directly from the MyConfig App. Both options allow the connection to be checked and modified via the ‘autowiring’ option, avoiding wiring errors and saving time during commissioning.

Applications

  • Measurement of electrical parameters in multi-channel installations, such as data processing centres and switchboards of single-phase loads.
  • Simultaneous measurement at 4 different points in three-phase installations
  • Its compact size is perfect for assembly on electric panels.

SPECIFICATIONS

Voltage measurement circuit
Voltage measuring range
120... 300 V~Ph-N / 120 ... 520 V ~ph-ph
Frequency measuring range
45…65 Hz
Input impedance
0,4 MΩ
Minimum measurement voltage (Vstart)
120 V ~
Installation category
CAT III 300 V
Sampling frequency
45…65 Hz
Maximum input voltage consumption
5…8 VA
Current measurement circuit
Nominal current (In)
... / 0,333 V
Maximum current
399 mV
Minimum current measurement
11 mV
Maximum input current consumption
0,18 VA x 4
Installation category
CAT III 300 V
Measurement accuracy
Phase voltage measurement
0,5%
Phase current measurement
0,5% (10… 120%)
Active power measurement (kW)
1%
Active energy measurement (kWh)
1%
Digital transistor outputs
Quantity
4
Type
NPN
Maximum voltage
24 Vdc
Maximum current
50 mA
Maximum frequency
5 imp/s
Pulse width
30 … 500 ms
Wireless communication
Technology / Type
Wi-Fi
Band
2,4 GHz (2,4…2,5 GHz)
Serial communication
Technology / Type
RS-485
Protocol
Modbus RTU
Communication Network
Technology / Type
Ethernet 10BaseT - 100BaseTX
Protocol
Modbus TCP - Web server - Web socket
Connection mode
DHCP ON/OFF
Connection mechanism
RJ-45
User interface
Display type
LCD
LED
2 LED
Keyboard
3 keys
Environmental characteristics
Working temperature
-10 ºC... +60 ºC
Storage temperature
10 ºC... +75 ºC
Relative humidity (without condensation)
5 ... 95%
Protection class
IP30, Front panel: IP41
Mechanical characteristics
Envelope
Self-extinguishing V0 plastic
Fastening
DIN rail
Weight (kg)
1,15
Size (mm) width x height x depth
105 x 104 x 72 (mm)
Standards
Standards
UNE-EN 61000-4-4, UNE-EN 61000-4-5, UNE-EN 61000-4-11,UNE-EN 61000-6-3, UNE-EN 61000-6-1, UNE-EN 61010-1, UNE-EN 60068-2-1, UNE-EN 60068-2-2,UNE-EN 60068-2-78, IEC 61010-2-030, IEC 61326-1, UNE-EN 61000-4-20, ETSI EN 301 489-1 V2.2.3, ETSI EN 301 489-17 V3.2.4
Electrical safety, Installation category
CAT III 300 V
Electrical safety, Contamination level/class
Pollution resistance 2
Electrical safety, Maximum height (m)
2000

DIMENSIONS

CONNECTIONS

VIDEOS

DOWNLOADS

User's manual
Technical guide
3D
Diagram connection
Datasheet
CE-certified

Certificates / Other downloads
Leaflet

ACCESORIES