Measuring transducers

CV-A Out1

CV-A Out1, Transducer Vac.

Code: M25031.

  • Output type: 1
  • Analog output: 0…20mA
  • Measure: 300 Vac
  • Paramètre: V ~

INFORMATION

Description

The CV-A transducers, convert A.C voltage to D.C process indicator signal.
The analog output is directly proportional to the input signal, calibrated as a RMS with sinus signal of 50 Hz.

SPECIFICATIONS

AC power supply
Nominal voltage
230 Vca
Frequency
40…90 Hz
Consumption
2,5 VA
AC power supply, insulation
Test voltage (kV)
3 kV RMS 50 Hz 1min
Pulse test (kV)
4 kV (1,2/50µs)
DC power supply
Nominal voltage
9…36 Vdc / 90…140 Vdc
Consumption
2,5 VA
DC power supply, insulation
Test voltage (kV)
2 kV RMS 50Hz 1 min
Pulse test (kV)
3 kV (1,2/50µs)
Voltage measurement circuit
Nominal voltage
0…660 Vca
Voltage measuring range
0…150 % Vn
Frequency measuring range
45…65 Hz
Input impedance
3000 Ω/V
Maximum permanent measurement voltage
1000 V
Measurement accuracy
Phase current measurement
0,2 % FS
Analogue outputs
Displaced output
0,2…2 V / 2…10 V / 4…20 mA
Current mode, nominal range
0…20 mA
Voltage mode: nominal output range
0…5, 10 Vac
Analogue inputs
Load impedance in voltage
> 500 Ω
Load impedance in current
< 500 Ω
Response time
< 300 ms (0…99 % Vn)
Ripple (effective RMS value)
< 0,5 %
Environmental characteristics
Working temperature
-10…+55 °C
Storage temperature
-40….+70 °C
Protection class
IP 20 (Terminals) IP 40 (case)
Standards
Standards
IEC 529, IEC 688, IEC 801, IEC 1010
Electrical safety, Maximum height (m)
2000
Mechanical characteristics
Weight (kg)
0,262
Size (mm) width x height x depth
40 x 72 x 110 (mm)

DIMENSIONS

CONNECTIONS

VIDEOS

DOWNLOADS

User's manual
Dimensions
Diagram connection
Datasheet

ACCESORIES

TAMBIÉN TE PUEDE INTERESAR