Current transformers and shunts

SH 300A/60mV

SH 300A/60mV, Shunt

Code: M7123A.

  • Accuracy: 0.5
  • Measurement Range (A): 300A/60mV
  • Input current: 300 A
  • Relation: 300A/60mV

INFORMATION

Description

  • Shunt for the measurement of DC, from 1 A dc to 15 000 A dc, depending on the type
  • Accuracy class: 0.5
  • All types are supplied with 1.5 m long cables, with a section of 1.5 m2
  • The standard output voltage is .../60 mV, but there are other types of outputs on demand, see coding table.

Applications

Used in DC electrical lines to obtain a voltage signal that is proportional to the current through the shunt

SPECIFICATIONS

Electrical characteristics
Permanent overload
1,2 In
Current measurement circuit
Primary current measurement
300 A
Allowable overload
During 5 s 10 In, yes 10 A ≤ In ≤ 500 A 5 In, yes 600 A ≤ In ≤ 2000 A 2 In, yes 2500 A ≤ In
Transformation ratio
…/ 60 mV
Nominal frequency
50 / 60 Hz
Measurement accuracy
Accuracy
0.5
Environmental characteristics
Working temperature
-25 … +60 ºC
Mechanical characteristics
Envelope
Manganin rods Brass terminals
Weight (kg)
0,8
Standards
Standards
DIN 43703, IEC 51, VDE 410, BS 89

DIMENSIONS

CONNECTIONS

VIDEOS

DOWNLOADS

3D
Dimensions
Datasheet
CE-certified

ACCESORIES