Current transformers and shunts

TP-23 50/5

TP-23 50/5, Split core current transformers

Code: M7011A.CONSULTAR DISPONIBILIDAD

  • System: Single-phase
  • Class 3 Power (VA): 1,5
  • Measurement Range (A): 50/5
  • Input current: 50/5 A

INFORMATION

Description

Open-core transformers that can measure current without having to interrupt the electric supply. In other words, the installation does not have to be dismantled in order to install them.

  • Range: 100 to 5000 A
  • Busbar dimensions: 20 x 30 mm to 80 x 160 mm
  • The transformer certificate is attached.

Applications

Converting a high nominal current to a lower current so that it can be measured by the unit. They have a split core and can be installed with no need to interrupt the installation's power supply.

SPECIFICATIONS

Electrical characteristics
Safety factor (SF)
FS 10
Power
1.5 VA (Class 3)
Current measurement circuit
Primary current measurement
50 A
Transformation ratio
… / 5 A
Nominal frequency
50 / 60 Hz
Dynamic current (Idyn)
2,5 Ith
Thermal short-circuit current (Ith)
60 In
Specific technical characteristics of current sensors
Operating voltage
0,72 kV~ max.
Environmental characteristics
Working temperature
-5 ... 40 ºC
Thermal Class
Class B (+130 ºC)
Standards
Standards
IEC 44-1, UNE 21 088-1, UL 94, VDE 0414
Mechanical characteristics
Weight (kg)
0,685
Size (mm) width x height x depth
110 x 89 x 58 (mm)

DIMENSIONS

CONNECTIONS

VIDEOS

DOWNLOADS

Datasheet
CE-certified

ACCESORIES




TAMBIÉN TE PUEDE INTERESAR