Current transformer with converter

TI-420-70-250A

TI-420-70-250A, Current transformer with converter 4 ... 20 mA

Code: M70822.

  • Inner diameter (mm): 70
  • Analog output: 4...20 mA
  • Measurement Range (A): 250
  • Input current: 250 A
  • Transformer type: Current transformer with 4 ... 20 mA converter

INFORMATION

Description

  • Needs an output power supply of 10 ... 28 V dc
  • Primary current: from 2.5 to 1500 A ~, depending on the type
  • Secondary current: 4 ... 20 mA
  • Internal diameter: from 35 to 105 mm, depending on the type
  • Busbar dimensions: from 35 to 105 mm, depending on the type

Applications

Used in power lines to obtain a current proportional to the primary current rated at 4 ... 20 mA in the secondary

SPECIFICATIONS

Auxiliary power supply
Voltage
10 … 28 Vdc
Mechanical characteristics
Size (mm) width x height x depth
130 x 110 x 33 (mm)
Weight (kg)
0,25
Environmental characteristics
Working temperature
-10°...+50 °C
Specific technical characteristics of current sensors
Inner diameter Ø (mm)
70
Operating voltage
0,72 kV~ max.
Current measurement circuit
Nominal frequency
50 / 60 Hz
Primary current measurement
250 A
Permanent overload
1,5 In
Transformation ratio
4 … 20 mA
Standards
Standards
IEC 44-1, UNE 21 088-1, IEC 664, VDE0110, VDE0414, UL 94, IEC 1010-1, EN 61010-1
Measurement accuracy
Accuracy
±1,5% In

DIMENSIÓN

VÍDEOS

DESCARGAS

Dimensions
Diagram connection
Datasheet
CE-certified

ACCESORIOS