Automatic capacitor banks with static contactor

OPTIM EMK6-400-440

OPTIM EMK6-400-440, Static capacitor bank

Code: R46431.

  • Cable section (mm2): 2x185
  • kvar (400 V): 331
  • kvar (440 V): 400
  • Optional circuit breaker (A) : 800
  • Optional manual switch (A): 800
  • Composition: 50 + 50 + 3x100
  • Use voltage (V): 440

INFORMATION

Description

The OPTIM-EMK-series capacitor banks have been designed for power factor correction in networks with fluctuating loads.

The power variations are relatively quick (measured in milliseconds) and the operation is thus carried out by thyristors, which are connected to a voltage controller board, so that the connection and disconnection of the capacitor is carried out with zero voltage difference.

Transients are prevented between the connection and disconnection of the steps, obtaining an immediate response to the load fluctuations.

Applications

The most common application is with individual loads or in installations where a quick compensation response is needed (for ex., welding units, motors for lifting units, lifts, etc.)

SPECIFICATIONS

Electrical characteristics
Voltage
400 V (other voltages on request)
Reinforcement voltage
440 V (400 V)
Surge
10 % 8 h over 24 h 15 % up to 15 min over 24 hours 20 % up to 5 min over 24 hours 30 % up to 1 min over 24 hours
Discharge resistance
75 V / 3 min
Current measurement circuit
Allowable overload
1,3 In
Permanent overload
1,3 In
Environmental characteristics
Working temperature
Tª class D: Daily average: 45 ºC, annual average: 35 ºC, maximum: 50 ºC, minimum: -25 ºC
Relative humidity (without condensation)
80%
Protection class
IP 21
Mechanical characteristics
Fastening
Vertical. Minimum distance between condensers 2 cm
Ventilation
Natural or forced according to options
Weight (kg)
262
Size (mm) width x height x depth
1200 x 1900 x 650 (mm)
Features / performance
Components
Three-phase measurement CLZ capacitor Static switching unit at each step, comprising static contactors (thyristors) Individual protection at each step via fuses with high cut-off power (APR), NH-00 or Neosted Series according to type Two-pole circuit breaker protection for battery and regulator operation Max Fast computer series reactive energy regulator Radiators for heat dissipation Thermostat built into the radiator itself to disconnect the step in case of high temperature (90 ºC)
Optional
Manual circuit breaker at capacitor bank header Circuit breaker at capacitor bank header Circuit breaker + earth leakage protection at capacitor bank header Forced ventilation unit + thermostat Polycarbonate plate to avoid direct exposure 400/230 V autotransformer
Standards
Standards
IEC 60831-1, IEC 70/7, UNE-EN 20827, UNE-EN 20010, BS 1650
Certifications
VDE 560
Electrical safety, Maximum height (m)
2000

DIMENSIONS

CONNECTIONS

VIDEOS

DOWNLOADS

User's manual
Dimensions
Diagram connection
Datasheet
CE-certified
Software & Firmware
Catalogue
Leaflet

ACCESORIES

TAMBIÉN TE PUEDE INTERESAR