Semi-fast hybrid automatic capacitor banks with phase-by-phase compensation for unbalanced networks

OPTIM HYB2-325-440

OPTIM HYB2-325-440, Capacitor bank

Code: R4E113.

  • Cable section (mm2): 2 x 150
  • kvar (400 V): 270
  • kvar (440 V): 325
  • Man.Switch (A): Included
  • Composition 230V/50Hz (Single-phase): (3 x 3 x 10) +
  • Composition 400V/50Hz (Three-phase): (3 x 60)
  • Use voltage (V): 440

INFORMATION

Description

The OPTIM HYB automatic capacitor banks with hybrid switching are units designed for automatic compensation of reactive energy in networks in which the load levels fluctuate, with power variation rates of seconds and also independently of the level of unbalance in the installation. The compensation system is based on the combination of switching by three-phase step contact breakers and single-phase step semiconductors (thyristors), controlled by a smart regulator that uses the electrical parameters provided via communications by a power analyzer of the CVM-MINI range for its calculations.

Applications

The OPTIM HYB series is ideal for achieving very accurate reactive power compensation in any installation, and especially those that present a certain degree of unbalance, since the compensation between phase and neutral adds to the fast reply provided by the static switching of the thyristor. It is therefore possible to guarantee a significant reduction in the chance of penalties in comparison with conventional capacitor banks.

SPECIFICATIONS

AC power supply
Frequency
50 Hz
Electrical characteristics
Losses (W)
< 0,5 W/kvar
Discharge resistance
75 V / 3 min
Surge
10 % 8 h over 24 h 15 % up to 15 min over 24 hours 20 % up to 5 min over 24 hours 30 % up to 1 min over 24 hours
Manoeuvre voltage
Contactors: 230 V
Reinforcement voltage
3 x 440 V F-F / 1 x 254 V F-N
Tolerance C
-5% / +10%
Mechanical characteristics
Size (mm) width x height x depth
800 x 1840 x 640 (mm)
Envelope
Steel sheet grey RAL 7035
Fastening
Vertical
Ventilation
Natural
Weight (kg)
42
Environmental characteristics
Protection class
IP 21
Relative humidity (without condensation)
80%
Working temperature
-25 … +45 ºC
Current measurement circuit
Allowable overload
1,3 In
Permanent overload
1,3 In
Standards
Electrical safety, Maximum height (m)
< 2000
Standards
IEC 61921, IEC 61642, IEC 60831
Features / performance
Components
Cylindrical capacitor, CLZ-FP type aluminium casing Reactive energy regulator, HYB computer communicating via RS-485 with a CVM-MINI-RS485 type power analyser
Optional
4-pole circuit breaker at capacitor bank header 4-pole circuit breaker + earth leakage protection at capacitor bank header
Protection
Circuit breaker type
Single or three-pole circuit breaker protection in each single or three-phase step

DIMENSIÓN

VÍDEOS

DESCARGAS

User's manual
Dimensions
Datasheet
Catalogue
Software & Firmware

ACCESORIOS